J-- Predefined parameter sets
(password-protected)
J1
Internal: Active data set
This parameter is used to set specific predefined data sets. The data sets are specified by Störk-Tronic. If a new data set is
imported, all previously set parameters are overwritten. They can then be freely changed.
J98
Password for entering the level selection
This parameter can be used to set the password for level selection, i.e. when
PA
is displayed. In the standard version,
access to the level selection is blocked with the password
-19
. This parameter cannot be set on the controller itself, but only
via the ST bus.
J99
Password for parameter level
J--
This parameter is used to set the password for parameter level
J--
. In the standard version, access to parameter group
J--
is blocked by password
- 19
.
L-- Networking and display
(password-protected)
L0
ST bus, own address
The controller can be addressed at the address set here via the bus. Each bus device must have its own address and no
addresses may occur more than once.
L2
: Temperature scale
If the value of the data transfer is a temperature, it is converted to the unit set here for the display.
L3
: Actual value display mode
The measured values can be rounded to half or whole numbers on request. All parameter settings and setpoints are
displayed with a resolution of 0.1 K.
L4
: Parameter address of displayed measured value
The measured values are arranged in a list and can be requested via an address within this list.
0
Display of the last temperature before defrosting
1
Cooling space temperature
2
Evaporator temperature
3
Evaporator fan variable
4
Cooling space setpoint
5
Condenser temperature
6
Condenser fan proportional result
7
Condenser fan variable
8
Condenser fan setpoint
9
Display via sample bottle
10
Min. temperature
11
Max. temperature
12
Circuit 2 temperature
13
Circuit 2 setpoint
14
Time
15
Sensor F1 direct
16
Sensor F2 direct
17
Sensor F3 direct
18
Sensor F4 direct
19
Sensor F5 direct
L6
Software version
The software version is displayed here.
L7
: Display during standby
The setting in
L7
can be used to specify how the standby state is displayed.
L40
Enable screen (bits 0..7)
L41
Enable screen (bits 8..15)
A binary screen is used here to specify which functions can be enabled using the bus. The bits have the following meanings: