L4
: Parameter address of the measured value
L4b
: Parameter address of measured value 2
The number of measured values the remote station addressed via
L1
makes available on the ST
bus is specified in the respective data sheet. The measured values are arranged in a list and can
be requested via an address within this list.
0
Display
11 Max. temperature
1
Cooling space temperature
12 Circuit 2 temperature
2
Evaporator temperature
13 Circuit 2 setpoint
3
Evaporator fan variable
14 Time
4
Cooling space setpoint
15 Sensor F1 direct
5
Condenser temperature
16 Sensor F2 direct
6
Condenser fan proportional result
17 Sensor F3 direct
7
Condenser fan variable
18 Sensor F4 direct
8
Condenser fan setpoint
19 Sensor F5 direct
9
Display via sample bottle
10 Min. temperature
L5
: Request cycle
The measured values are requested periodically. The display is updated at the same rate.
L6
: Software version
L7
: Display during standby
The current status of the remote station is queried cyclically with the setting
L9
= 0. The setting in
L7
can be used to specify how the "OFF" state of the remote station is displayed. If
L9
= 1, the
setting in
L7
is ignored.
L8
: Key lock function
This parameter is used to set whether the setpoint, own parameter or external parameter may be
displayed and/or adjusted via the keys. In the "0" setting, everything is permitted; in the "4" setting,
all parametrisation is disabled. If
L8
= 5, any available function keys are also deactivated.
L8
Description
0
No key lock, setpoint and parameters are visible but can be adjusted.
1
No key lock, the setpoint can be displayed but not adjusted, the parameters of levels
PA
and
PAE
are freely accessible and can be adjusted.
2
SET key for setpoint is disabled, i.e. the setpoint cannot be displayed or adjusted.
Parameter levels
PA
and
PAE
are freely accessible and can be adjusted.
3
As 2, but the parameters can only be displayed, not adjusted.
4
As 2, but only local level "
PA
" is visible and only "
L8
" can be adjusted.
5
As 4, but all function keys are locked (e.g. standby).