SM-ASB Instruction Manual V1.0- 2/4/08

100.00

mm

29.0 mm

36.0 mm

1

2

3

45

6

7

8

Mechanical Specification

Weight

Base Sounder - 100 g

including Lid - 120 g

including electronic circuits

and fixings

Enclosure Construction Material

Flame Retardant rating 94V0

White ABS - Transparent PC

Technical Specifications

Operating Voltage

Sounder Output

Flash Colour

Flash Rate

Alarm Tone

Current Consumption

Quiescent

Sounder Only

Flasher Only

Combined Sounder Flasher

Compatible Detectors

800-970Hz (0.5s each)

17-30V DC

85 dB @ 1 metre

Red

0.3 Hz

(Add 12 mA when conventional detector is in alarm)

1.2 mA + conventional detector quiescent current

4 mA

2.5 mA

5.5 mA

FEOE2000, FEOH2000, FEHE2000, FEFHE2000

The Securetone Micro Addressable sounder
flasher base is the latest innovative product
from GLT Exports Ltd. It is available as an
addressable sounder, or combined sounder
flasher, to which can be connected a
conventional detector, either smoke, heat, or
opto-heat. This can allow for considerable
cost savings in locations where a sounder &
detector are required. It is designed to work
with Zeta Analogue addressable control
panels only.

The Securetone Micro sounder has an 8 way
D.I.L. switch to set the address. Switch 8
MUST be to the ON position. Switches 1 to 7
are used to set a binary address, with OFF
being a binary 1, and ON being a binary 0 (or
see setting chart on page 3)

There is a jumper to tell the sounder whether a
conventional Optical smoke detector, or
conventional heat detector has been fitted.
This makes the sounder reply as OPTICAL, or
HEAT.

There is also a potentiometer which may be
used to adjust the sound level if required. It is
supplied set to it`s maximum volume.

Normally the

will be used

in conjunction with a conventional heat/
smoke detector. However, if the MODE
selection jumper is removed, it will behave as
a normal addressable sounder. (NOTE: in this
configuration, the conventional detector input
will be inoperative.)

The sounder flasher version also includes a
loop short circuit isolator, which minimises
the number of devices which would be
inoperative in the case of a short circuit on the
loop.

Securetone Micro

Low current consumption.
5.5 mA for combined Sounder/Beacon

Address setting is in the base for easy
Detector head replacement

Can work as a stand alone sounder.

Complies with EN-54 pt.3

Allows use of Conventional Detectors

Loop Isolator option

Compatible with all Zeta addressable panels

Features

ORDER CODE PRODUCT DESCRIPTION

SECURETONE MICRO ADDRESSABLE SOUNDER BASE

SECURETONE MICRO ADDR. SOUNDER FLASHER BASE with ISOLATOR

LID FOR SOUNDER BASE (WHITE)

LID FOR SOUNDER BASE (TRANSPARENT-CLEAR)

LID FOR SOUNDER BASE (TRANSPARENT-RED)

SM-ASB

SM-ASFIB

V2 L

V2 LT

V2 LTR

Addressable
Sounder/Flasher Base

to

e

cu

r

e

S

e

n

Micro

Loop Out

LoopIn

Mode

-V

ol

+

Sounder Flasher
with Short Circuit
Loop Isolator

Sounder

to

e

cu

r

e

S

e

n

Micro

Heat
Detector
Smoke
Detector

Addressable
Sounder/Flasher Base

|S

Address

MODEL

SM-ASFIB

SM-ASB

SWITCH

8

M

UST

BE

IN

ON

POSITION

1

Отзывы: