Assembly-Programming-Instructions_Cold-Rack_e_05-10-2018
Page 34
Parameter
Functional description
Setting range
Factory values
Customer
values
Arctis/
Duplex
Vulcano Cold
Rack/
Showca
ses
d7
Temperature difference to the cooling
space setpoint with previous cooling
down.
- 15 °C ... 0.0 °C
0.0
0.0
0.0
d8
Time limit with previous cooling down.
1 ... 180 min
10
10
10
d9
Delay time for defrost start after
compressor off
d2
= 2
0 ... 900 s
60
60
60
d10
Drip off time .
0 ... 15 min
1
1
1
d11
Drip tray heating run-on time.
0 ... 60 min
10
10
10
d20
Display forced release after defrosting. 0 ... 60 min (0 = no forced release)
5
5
5
d99
Password for parameter level
d--
- 99 ... 999
0
0
0
F--
Fan control loop 1
Parameter
Functional description
Setting range
Factory values
Customer
values
Arctis/
Duplex
Vulcano Cold
Rack/
Showca
ses
F8
Fan speed standard operation, Set1.
0 ... 98 %
55.0
35.0
70.0
36.0
F9
Defrost fan speed, Set1.
0 ... 98 %
98.0
98.0
98.0
F10
Control mode fan speed, Set2.
0 ... 98 %
80.0
80.0
80.0
F11
Defrost fan speed, Set2.
0 ... 98 %
98.0
98.0
98.0
F12
Start boost time.
0 ... 60 s
5
5
5
F13
Minimum speed (output variable with
result = 0).
0 ... 98 %
40.0
40.0
40.0
F15
Evaporator fan. Normal operation fan
mode. Remark: Control setpoint with
F15 >
4 is
c1
or
c3
0: Off
1: Continuously running
2: As 1, with drip interruption
3: With compressor on
4: Temperature-controlled, evaporator
sensor only
5: Temperature-controlled, difference
of cooling space to evaporator sensor
1
1
1
F16
Evaporator fan, defrost fan mode.
0: Off
1: On
1
1
1
F17
Evaporator fan, delay after compressor
start.
0 ... 600 s
0
0
0
F18
Evaporator fan, delay after defrosting.
0 ... 600 s
0
0
0
F19
Evaporator fan, drip interruption time
with
F15
= 2
0 ... 600 s
0
0
0
F20
Evaporator fan, control offset with
F15
= 4 or 5
- 15.0 ... + 15.0 °C
0.0
0.0
0.0
F21
Evaporator fan, control hysteresis with
F15
= 4 or 5
0.1 ... 15.0 °C
2.0
2.0
2.0
F50
Condenser sensor assignment.
Detailed description of the sensors in
parameters
H11
to
H53
0: None
1: Sensor F1
2: Sensor F2
3: Sensor F3
4: Sensor F4
5: Weighted average of F1 and F2
0
0
0
F51
Condenser fan setpoint.
- 55...+ 150 °C
60.0
60.0
60.0