Bit
Value Function
L40
0
1
Controller on/off
1
2
Control loop 1 on/off
2
4
Control loop 2 on/off
3
8
Control loop 1: Defrosting request
4
16
Control loop 1: Superfrost request
5
32
Control loop 1: Reserved
6
64
Control loop 1: Set1/Set2 changeover
7
128 Control loop 1: Day/night changeover
L41
8
1
Control loop 2: Defrosting request
9
2
Function A (light 1)
10
4
Function B (light 2)
11
8
Function C
12
16
Function D
13
32
Function E
14
64
Function F
15
128 Reserved
To determine the value to be parametrised, the corresponding values must be added together.
L42
Enable for deleting counters/run times
Here, the deleting of the run times, the relay counters and the min./max. memory is enabled for 10 minutes. The parameters
T98, N98 and A17 can only actively delete the corresponding timers, counters or memory locations within these 10 minutes.
After the 10 min expire, the enable is removed. The deleting of the min./max. memory by a function assignment of the keys
is not affected by this.
L99
Password for parameter level
L--
This parameter is used to set the password for parameter level
L--
.
U-- Relay contacts and lamps
(password-protected)
U1
...
U8
Function of relays K1...K8
Assignment of the internal output signals to the corresponding relays.
U9
Function of triac
U10
Triac power limitation function
With
U9
, any function can be assigned to the triac. If the selected signal is active, the output is set to the limit set in parameter
U10
. The limitation is to be evaluated differently depending on the connected consumer. In the [
U9 = 4
] setting (condenser
fan), the
F50
–
F68
parameters are also evaluated. The
U10
parameter limits the max. signal.
U11
Upper limit
U10
U12
Lower limit
U10
The power limitation can only be set within the limits specified here.
U99
Password for parameter level
U--
This parameter is used to set the password for parameter level
U--
.