J-- Predefined parameter sets
Parameter
Functional description
Setting range
Factory values
Customer
values
Arctis/
Duplex
Vulcano Cold
Rack/
Showca
ses
J1
Parameter set.
0 ... 1
0
0
0
J99
Password for parameter level
J--
- 99 ... 999
0
0
0
A-- Function
Parameter
Functional description
Setting range
Factory values
Customer
values
Arctis/
Duplex
Vulcano Cold
Rack/
Showca
ses
A1
Dim first display.
5…100
100
100
100
A2
Dim second display (if present).
5…100
100
100
100
A3
Dim LEDs.
5…100
50
50
50
A4
Type of controller connected.
0: Standard 112 (
→
Adr Con PA PAE
)
1: ST-Box (
→
PA PAE
)
1
1
1
A5
Restrict access to
USr
level.
0: All levels free
1: Only
USr
level accessible
0
0
0
A99
Password for access to parameter list
P--
- 99...999
- 19
- 19
- 19
Parameter description:
Ver. 1.11
L0
: ST BUS, own address
Each bus device is given a bus address that must be unique.
L1
: ST BUS, address of the remote station
Address of the remote station that provides a measured value.
L2:
Temperature scale
If the value of the data transfer is a temperature, it is converted to the unit set here for the display.
L3
: Actual value display mode
The measured values sent from the controller to the satellite always have the highest resolution,
but the satellite display can round the measured values to half or whole numbers if required. All
parameter settings and setpoints are displayed with a resolution of 0.1 K.
Attention:
Any change to the parameter set changes all parameter setting!
!