4.3
Status messages
Master password
All passwords can be changed by parametrisation. If the user forgets the password, it is
still possible to parametrise the controller via a master password and, in particular, to
check and/or change the forgotten password. This requires the following steps:
1. Switch off the power supply to the controller (disconnect from the mains or switch off
the power supply unit).
2. Press the
UP
,
DOWN
and
SET
keys simultaneously and switch on the power supply
again.
3. A ("challenge") number now appears on the display for approx. 5 s. Do not disconnect
the controller from the power supply now because this would invalidate the number.
Use this number to call our sales department, Tel. +49 711 68661 0 and receive the
master password ("response"). Enter this master password at the 1st operating level
for
PA
.
Important: Even if the user has not forgotten this password, the master password must be
entered here. If the password is accepted, the user is in the parameter level selection and
all passwords are deactivated. The user can change to the corresponding parameter level
simply by pressing the
SET
key (
---
display).
The master password is no longer required. The passwords remain deactivated until the
controller is disconnected from the power supply. If the user leaves the parameter level, it
is sufficient to simply press the
SET
key for
PA
to return to the selection of the parameter
levels.
4.4
Error messages
Message
Cause
Measure
H1
Overtemperature, temperature above the alarm
limit from parameter
c7
L0
Undertemperature, temperature below the alarm
limit from parameter
c8
E1L
Fault on sensor F1, short circuit.
Check sensor F1
E1H
Fault on sensor F1, breakage.
Check sensor F1
E2L
Fault on sensor F2, short circuit.
Check sensor F2
E2H
Fault on sensor F2, breakage.
Check sensor F2
E3L
Fault on sensor F3, short circuit.
Check sensor F3
E3H
Fault on sensor F3, breakage.
Check sensor F3
E4L
Fault on sensor F4, short circuit.
Check sensor F4
E4H
Fault on sensor F4, breakage.
Check sensor F4
E5
Door open too long.
Close the door
E6
High-pressure fault.
Check: Condenser fan and soiling
E7
Low-pressure fault.
System leaking, insufficient cooling agent
E10
External alarm.
EP0
Internal controller fault.
Repair the controller
EP1
Error in the parameter memory.
Check all parameters
EP2
Error in the data memory.
Repair the controller
Pr
Internal: Test mode.
Briefly disconnect the controller from the mains voltage; if
the message does not disappear -> repair
rtc
Internal clock error.
Reset clock; if the error does not disappear -> repair
The errors
EP0
and
EP1
block the control system. The control system is not enabled until the error has been eliminated. The error(s)
EP0
(and
EP2
) can only be corrected by repair. The errors are displayed alternately with the currently measured temperature.