14/4798.495.002
Installation | 79
Dachs Pro 20 ST
6.10.3 Connection of the CO sensors to the CHP
6.10.4 MSR Pro 20 ST grid connection
Fig. 73: CO sensors
Fig. 74: CO sensor positioning
Fig. 75: Grid connection at the MSR Pro 20 ST
Fig. 76:
X0
grid connection in the MSR Pro 20 ST
►
Install the two provided CO sensors inside the installation
room according to the manufacturer instructions.
●
The electrical grid connection is to
be realised according to the provided
schematic diagrams.
Separate supply with
3 × 1.5 mm²
►
Remove one stepped nipple at the
rear of the controller housing.
►
Slide the removed stepped nipple
over the grid supply.
►
Insert the grid supply from the outside
into the controller.
►
Secure the stepped nipple inside the
controller housing.
►
Connect the
L, N
and
PE
ports of the
supply to the spring type terminals at
the
X0
connection bar.
►
Secure the grid supply with 2 cable
ties at the strain relief rail.
Reference:
For CO sensor assembly and connection to the CHP,
please observe the instructions and information in
the iav Documentation of VW on the EcoBlue 2.0
(Generation 1.2) in particular. For example:
●
VW EcoBlue 2.0 (Generation 1.2) installation
manual for Dachs Pro 20 ST
, art. no. 4798.522.
xxx
- particularly chapter 6.12
.
●
Circuit diagram extracts - VW EcoBlue 2.0
(Generation 1.2)
, art. no. 4798.537.xxx.
powered by
Volkswagen
3 ×
1.5 mm²
Attention:
Ensure secure fi tting of the
connection at the spring-type
terminals of the
X0
connection bar.
!
X0
Содержание Senertec Dachs Pro 20 ST
Страница 115: ...14 4798 495 002 Spare parts 115 Dachs Pro 20 ST Notes ...
Страница 116: ...14 4798 495 002 116 Spare parts Dachs Pro 20 ST Notes ...
Страница 117: ...14 4798 495 002 Spare parts 117 Dachs Pro 20 ST Notes ...
Страница 118: ...Dachs Pro 20 ST Baxi Commercial Wood Lane Erdington Birmingham B24 9QP ...