14/4798.495.002
Installation | 75
Dachs Pro 20 ST
*
The generator unit supplies additional power. For cable and line protection,
an additional fuse may be required (DIN VDE 0100-430).
Mains connection at meter panel
and existing power distribution panel
Mains connection at existing
power distribution panel
Low voltage grid of the VBN ~ 400/230 V
Low voltage grid of the VBN ~ 400/230 V
Z1
Z1
Z2
Z2
Meter panel
Meter panel
Power distribution panel
(sub-distribution)
Power distribution
panel (sub-distribution)
*
*
(FI)
(FI)
B 16A
B 16A
SCHEMATIC DRAWING - NO CONNECTION DIAGRAM!
Controller
MSR Pro 20 ST
MSR Pro
20 ST controller
min. 5 x
10 mm
2
Cu
min. 5 x
10 mm
2
Cu
e.g. D0 circuit
breaker (Neozed)
50gG
CHP
Electricity meter
CHP
Electricity meter
e.g. D0 circuit
breaker (Neozed)
50gG
powered by
Volkswagen
powered by
Volkswagen
Dachs Pro 20 ST
Dachs Pro 20 ST
RCD
I
∆n
30 mA
RCD
I
∆n
30 mA
Z1:
Meter for consumption and supply (bidirectional meter)
Supply: Metering of the supply into the grid of the distribution network operator for sale, e.g.
according to market conditions (European Energy Exchange) and avoided network tariff s
Z2:
Meter for metering the generated CHP net electricity (meter with non-return device)
RCD:
Residual current device
Fig. 64: Schematic diagram of Dachs Pro 20 ST grid connections
Содержание Senertec Dachs Pro 20 ST
Страница 115: ...14 4798 495 002 Spare parts 115 Dachs Pro 20 ST Notes ...
Страница 116: ...14 4798 495 002 116 Spare parts Dachs Pro 20 ST Notes ...
Страница 117: ...14 4798 495 002 Spare parts 117 Dachs Pro 20 ST Notes ...
Страница 118: ...Dachs Pro 20 ST Baxi Commercial Wood Lane Erdington Birmingham B24 9QP ...