Integrated safety functions
350
ACOPOSinverter P84 User's Manual 2.10
Required safety function level (SF) for the PWR (STO) function
Configuration
SIL (Safety Integrity Level ) per IEC 61-50
PL (Performance Level) in accordance with
ISO-13849
PWR (STO) with or without a safety switching de-
vice
SIL 2
PL "d"
Therefore, for the following reasons the safety switching device (or equivalent equipment) must be used in the
vicinity of the machine:
•
In the vicinity of the machine (IEC 60204-1 and machine directive) a reset is not permitted to trigger a
restart under any circumstances. There is a particularly compelling case if the voltage supply is switched
off during the activation of the function PWR (STO). In this case, if PWR (STO) has been disabled during
the interruption of the power supply, the motor is not permitted to be restarted automatically under any
circumstances. The safety switching device can prevent an unwanted restart under this condition. The
safety switching device is therefore mandatory for machine applications.
•
E_STOP of several BDM in a PDS: The safety switching device has some safety outputs for applications
that require one or several safety outputs.
The safety relay is not necessary in other environments unless required by the application: Fallback position of
the system
Содержание ACOPOSinverter P84
Страница 2: ......
Страница 384: ...Accessories 384 ACOPOSinverter P84 User s Manual 2 10 8I0FT180 300 1 A Nm lb in 8I0FT180 300 1 25 221 3...
Страница 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Страница 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Страница 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Страница 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Страница 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Страница 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...