Programming guidelines
ACOPOSinverter P84 User's Manual 2.10
305
[BRAKE RESIST PROTECTION ](brP-) and AUTO-TUNE FAULT] ( tnF-)
Code
Name/Description
Setting range
Factory settings
brP-
[BRAKE RESIST PROTECTION]
brO
[Braking resistor protection response]
[No]
(nO)
nO
[No]
(nO)
: No braking resistor protection (this prevents access to the other parameters of the function).
YES
[Alarm]
(YES)
: Alarm. The alarm can be assigned to a logic output or a relay.
FLt
[Fault]
(FLt)
: Change to the fault
(bOF)
with locking of the inverter (freewheel stop).
Note:
The thermal state of the resistance can be displayed on the graphic display screen. It is calculated as long as the inverter control
is connected to the power supply.
brP
[Brake resistor power]
0.1 to 1000 kW
0.1 kW
This parameter can be activated if
[Braking resistor response]
(brO)
is not equal to
[No]
(nO)
.
Nominal power of the resistance used.
brU
[Brake resistor value]
0.1 to 200 Ω
0.1 Ω
This parameter can be activated if
[Braking resistor response]
(brO)
is not equal to
[No]
(nO)
.
Nominal value of the braking resistor in ohms.
tnF-
[AUTO TUNING FAULT]
tnL
[Autotune fault mgt]
[freewheel stop]
(YES)
nO
[No]
(nO)
: Fault is ignored.
YES
[freewheel stop]
(YES)
: Freewheel stop
Parameter that can be modified during operation or when stopped.
Содержание ACOPOSinverter P84
Страница 2: ......
Страница 384: ...Accessories 384 ACOPOSinverter P84 User s Manual 2 10 8I0FT180 300 1 A Nm lb in 8I0FT180 300 1 25 221 3...
Страница 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Страница 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Страница 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Страница 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Страница 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Страница 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...