Programming guidelines
ACOPOSinverter P84 User's Manual 2.10
147
Code
Name/Description
Setting range
Factory settings
SP2
[Preset speed 2]
0 to 599 Hz
10 Hz
see "PRESET SPEEDS (PSS-)" on page 211
2nd preset frequency
SP3
[Preset speed 3]
0 to 599 Hz
15 Hz
3rd preset frequency
SP4
[Preset speed 4]
0 to 599 Hz
20 Hz
4th preset frequency
SP5
[Preset speed 5]
0 to 599 Hz
25 Hz
5th preset frequency
SP6
[Preset speed 6]
0 to 599 Hz
30 Hz
6th preset frequency
SP7
[Preset speed 7]
0 to 599 Hz
35 Hz
7th preset frequency
SP8
[Preset speed 8]
0 to 599 Hz
40 Hz
8th preset frequency
SP9
[Preset speed 9]
0 to 599 Hz
45 Hz
9th preset frequency
SP10
[Preset speed 10]
0 to 599 Hz
50 Hz
10th preset frequency
SP11
[Preset speed 11]
0 to 599 Hz
55 Hz
11th preset frequency
SP12
[Preset speed 12]
0 to 599 Hz
60 Hz
12th preset frequency
SP13
[Preset speed 13]
0 to 599 Hz
70 Hz
13th preset frequency
SP14
[Preset speed 14]
0 to 599 Hz
80 Hz
14th preset frequency
SP15
[Preset speed 15]
0 to 599 Hz
90 Hz
15th preset frequency
SP16
[Preset speed 16]
0 to 599 Hz
100 Hz
16th preset frequency
MFr
[Multiplying coeff.]
0 to 100%
100%
Access to the coefficients is possible if
[Multiplier ref. -]
(MA2,MA3)
(
see "CONFIG REF (OAI-)" on page 203
) has been assigned to the graphic
display terminal.
SrP
[+/-Speed limitation]
0 to 50%
10%
see "+/- SPEED BY REFERENCE (SrE-)" on page 215
.
Limitation of +/- speed variation.
rPG
[PID prop. gain]
0.01 to 100
1
see "PID CONTROLLER (Pld-)" on page 239
Proportional amplifier
rIG
[PID integral gain]
0.01 to 100
1
see "PID CONTROLLER (Pld-)" on page 239
Integral gain
rdG
[PID derivative gain]
0.00 to 100
0
see "PID CONTROLLER (Pld-)" on page 239
Derivative gain
PrP
[PID ramp]
0 to 99.9 s
0
see "PID CONTROLLER (Pld-)" on page 239
Ramp-up/down ramp of the PID, which is set for a range of
[min PID ref]
(PIP1)
to
[max PID ref]
(PIP2)
or vice versa.
POL
[Min PID output]
-500 to +500 or -599 to
599, depending on the size
0 Hz
see "PID CONTROLLER (Pld-)" on page 239
Minimum value of regulator output in Hz.
POH
[Max PID output]
0 to 500 or 599, de-
pending on the size
60 Hz
see "PID CONTROLLER (Pld-)" on page 239
Maximum value of regulator output in Hz.
PAL
[Min fbk alarm]
1)
100
see "PID CONTROLLER (Pld-)" on page 239
Minimum monitoring threshold for regulator feedback.
PAH
[Max fbk alarm]
1)
1000
see "PID CONTROLLER (Pld-)" on page 239
Maximum monitoring threshold for regulator feedback.
1)
If there is no graphic display terminal, then on the four-digit display the values over 9999 are shown with one point after the thousands unit, for example,
15.65 for 15650.
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can also be
accessed and adjusted from within the configuration menu for the corresponding function, their description is detailed in these menus, on
the pages indicated, to aid programming.
Содержание ACOPOSinverter P84
Страница 2: ......
Страница 384: ...Accessories 384 ACOPOSinverter P84 User s Manual 2 10 8I0FT180 300 1 A Nm lb in 8I0FT180 300 1 25 221 3...
Страница 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Страница 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Страница 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Страница 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Страница 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Страница 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...