Axell D-MBR 3007-3008-PS-NFPA
PRODUCT DESCRIPTION AND USER’S MANUAL
© Axell Wireless Ltd
UMCD00013 Rev 2.2
3
1.2 Repeater Model
ORDERING INFORMATION
Identification
Description
Part Number
D-MBR 3007-3008
PS NFPA AC
Digital Multi Channel Selective Repeater
700/800 12 channels,
30 dBm output power per band, 85 dB
gain,
AC
powering with NFPA and IFC
compliant Alarm Outputs, Red colored
case
D-MBR 7/8 PS
30DBM 12 FIL NFPA
RED
D-MBR 3007-3008
PS NFPA DC
Digital Multi Channel Selective Repeater
700/800 12 channels,
30 dBm output power per band, 85 dB
gain,
DC
powering with NFPA and IFC
compliant Alarm Outputs, Red colored
case
D-MBR 7/8 PS
30DBM 12F NFPA
DC
1.3 NFPA Installation Architecture
To meet the National Fire Protection Association (NFPA) requirements, power to the
Repeater is provided via a UPS and the status of the UPS, Repeater and DAS system
(antennas) is monitored via alarm connections to the Fire Department Control Box.
NOTE: An alternative to the
F
ire Department Control Box connections is to connect the D-MBR PS
NFPA and UPS dry contact alarms to an Automatic Dialer. Axell Wireless recommends the AD-2000
Automatic Voice/Pager Dialer System.
The alarms are connected as follows:
•
From the UPS - the power indicator alarms are connected directly to the Fire
Department Control Box.
•
From the Repeater – the Repeater status and antenna status alarms are connected
to the Control Box
Figure 1-1. D-MBR PS NFPA Architecture