Axell D-MBR 3007-3008-PS-NFPA
PRODUCT DESCRIPTION AND USER’S MANUAL
© Axell Wireless Ltd
UMCD00013 Rev 2.2
35
4.4
Configuring the External Alarms
Any connected
external
alarms (section 3.9) must be enabled and configured according
to the instructions provided in this section.
To configure external alarms
1. Click on
CMU
in the tree pane and select the
External Alarms
tab. The following
dialog appears.
Figure 4-6. External Alarm Configuration Dialog
2. For each connected alarm:
•
Checkmark the
Active
checkbox.
•
Verify the alarm
Normal Mode
is set to Low.
•
Set the alarm
Severity
as Critical, Major or Minor
•
In the
Description
field, assign the alarm an identifiable name (e.g. Door
open).
NOTE: Triggered external alarms are displayed in the
Axell-CMU-Alarms
tab.
Click
CMU
External
Alarms tab