AXELL D-MBR 3007-3008-PS NFPA REPEATER
PRODUCT DESCRIPTION AND USER’S MANUAL
48
UMCD00013 Rev 2.2
© Axell Wireless Ltd
6.2
GUI Alarm Descriptions
The Alarms tab provides the alarms generated by the Repeater, enabling the user to
monitor the system operation.
To access the Alarms window
From the Tree Pane, select the 700/800 item and choose the
Alarms
tab. Note that some
alarms are dedicated for the UL and DL and other alarms are common to the UL and DL.
NOTE: Use the Ack All button to simultaneously acknowledge all triggered alarms.
Alarm
Fault and most probable cause and Recommendation
System Mute
Description.
Generates an alarm when Repeater amplification is
automatically
muted.
Possible causes:
•
Temperature failure
•
Synthesizer failure
•
Hardware failure
•
High RSSI power DL/UL when the shutdown mechanism is on
(Control and Params tab).
Recommended action:
Check the LEDs and other alarm from
the Repeater. Contact Axell Support
User Mute
Description:
Manual shutdown performed by operator from the
Web GUI.
Recommended action:
Review unit’s log
Built In Test
Possible causes:
Hardware failure, Circuitry failure, Software
failure
Recommended action:
Contact Axell Support
Temperature
Description:
Repeater temperature is exceedingly high due to
excessive external heat.
Ack All
triggered
alarms