3.4
Mounting the D-MBR
3.4.1 Pre-Mounting Procedure
1. Choose the location of the Repeater on the wall according to the following criteria:
•
The location should be at normal eye level height, above ground.
•
Be sure to allow easy access to the Repeater for maintenance and on-site
inspection.
2. Place the Mounting Bracket against the wall and mark the
four
holes to be drilled at
the extreme four corners of the bracket (additional optional installation holes are
also provided).
3. Drill four holes 12mm in diameter and 65mm in depth.
The following illustration shows the bracket with the bracket pins.
NOTE: The NFPA bracket
may
be colored
RED
.
Figure 3-2. D-MBR 3007-3008-PS-NFPA-A Mounting Holes and Pins
Optional
installation holes
Optional
installation holes
2x bottom holes
2x top holes
Assembled PS