Station circuit distribution from equipment room
Issue 3 January 2008
45
If most of the telephones/voice terminals that require remote powering are within 250 feet (76.2
meters) of the equipment room, 4-pair station circuits are run from the equipment room to the
information outlets. If this is not the case, or if the customer requires 2-point administration,
3-pair station circuits are run from the equipment room to satellite locations. Then, the 4-pair
station circuits are run from the satellite locations to the information outlets.
This section has information about
●
4-pair station circuits
on page 45
●
3-pair to 4-pair station circuit distribution
on page 45
●
Connected cable station adapters
on page 50
Lists of telephones and consoles currently sold are provided in
Table 7: Connectable telephone
and consoles
on page 70.
4-pair station circuits
Four-pair circuits, via station cables, can be run directly from an equipment room MDF to a
258A or BR2580A adapter as shown in
Figure 18: 4-pair circuit distribution and connectivity
on
page 46. The 4-pair station cables connect the adapter to the information outlets.
The 4-pair station cables can be run directly from the equipment room to the information outlets
if 4-pair terminal blocks are used in the distribution field. See
Figure 19: 4-pair run to equipment
room or satellite location
on page 47. The station cables must be field-terminated on the
110-type terminal blocks.
If 110-type terminal blocks are used with a modular plug-ended station cable, an adapter can be
connected directly to the 110-type terminal block connectors. See
Figure 20: 4-pair run to
equipment room or satellite location
on page 47.
3-pair to 4-pair station circuit distribution
Figure 21: 3-pair to 4-pair satellite location connectivity
on page 48 shows the 3-pair circuit
distribution from an equipment room MDF to a satellite location using 110-type hardware.
Four-pair circuits are distributed from the satellite location to the information outlets.
Three-pair circuits can also be run directly from the equipment room MDF to a 356A adapter as
shown in
Figure 22: 3-pair to 4-pair circuit distribution and connectivity
on page 49. Four-pair
station cables connect the adapter to the information outlets. Four-pair station cables can be run
directly from a satellite location to the information outlets as previously described.
Note:
Note:
Bridged taps are not allowed on any part of the station wiring.
Содержание 03-300686
Страница 1: ...Installing and Connecting the MDF and Telephones 03 300686 Issue 3 Release 5 0 January 2008 ...
Страница 8: ...Contents 8 Installing and Connecting the MDF and Telephones ...
Страница 28: ...Installing the main distribution frame 28 Installing and Connecting the MDF and Telephones ...
Страница 32: ...Installing the patch panel 32 Installing and Connecting the MDF and Telephones ...
Страница 40: ...Media gateway connections to the MDF 40 Installing and Connecting the MDF and Telephones ...
Страница 53: ...Completing a provisioning plan Issue 3 January 2008 53 Figure 25 Port Assignment Record Form ...
Страница 108: ...Installing and wiring telephones and trunks 108 Installing and Connecting the MDF and Telephones ...
Страница 134: ...Installing and wiring telephone power supplies 134 Installing and Connecting the MDF and Telephones ...
Страница 156: ...156 Installing and Connecting the MDF and Telephones Index ...