45
speed can be adjusted through the button of “wind speed selection” in the selection of the four wind
speeds type, such as strong wind, high wind, low wind and mute wind. The four-way valve always is
closed under this mode. The other action is as following:
①
When TA - TS
≥
1
℃,
after the compressor meet the 3 minutes delay protection, the compressor and
the outdoor fan start running;
②
When TA = TS
,
maintain the previous status;
③
When TA - TS
≤
-1
℃,
after the compressor meet the 3 minutes protection condition, the compressor
and the outdoor fan turn off;
④
The setting wind speed can be adjusted by the remote control during the ongoing cooling process,
and the interior fan still retains working;
⑤
When the status of TE
≤
0
℃
last for 10 seconds and the compressor keeps working for above than 5
minutes, turn off the compressor and outdoor fan, the indoor fan keep working according to the setting
wind speed; Quit from such protection if TE
≥
7
℃
;
⑥
This mode includes the functions of timing, sleeping, auto-restart (optional), negative ion (optional),
I feel
(
optional
)
;
⑦
When the cooling ongoing
,
the button of the “Swing” can control the swing and stop of the
horizontal air-blade;
⑧
Automatic wind-speed control
:
TA - TS
≥
3
℃,
wind-speed works at high wind;
TS +1
℃
≤
TA
<
TS +3
℃,
wind-speed works at middle wind;
TA – TS
<
1
℃,
wind-speed works at low wind;
Without 3 minutes delay when the wind speed turns into the high wind from the low wind, otherwise
with 3 minutes delay;
⑨
Being initially electrified, the compressor doesn’t have the 3 minutes delay protection, the outdoor
fan starts after 2 seconds of the compressor’s start; When TS
>
TA set by the remote control, the
compressor turns off immediately with no need of 3 minutes delay protection;
⑩
When TE
≥
64
℃
and after last for 10seconds, the compressor and the outdoor fan turn off; If meet
the 3 minutes delay condition and TE
≤
62
℃
, the compressor can start normally. When the
air-conditioner is under overheating protection, if the wind speed setting is by hand, the indoor fan
unit will run at the setting wind speed; if the wind speed setting is automatic, the indoor fan unit runs
at the low fan speed.
⑸
Dehumidification mode
①
The four-way valve always turns off when the dehumidification mode is ongoing. The control range
of the temperature is: 16
℃
- 32
℃
.
Содержание E Series
Страница 1: ......
Страница 32: ...AUX air conditioner service manual The other parts 29 ...
Страница 33: ...AUX air conditioner service manual 30 ...
Страница 102: ...AUX air conditioner service manual 99 Outdoor unit exploded picture ...
Страница 104: ...AUX air conditioner service manual 101 2 ASW H09A4 EC Indoor unit exploded picture ...
Страница 106: ...AUX air conditioner service manual 103 Outdoor unit exploded picture ...
Страница 108: ...AUX air conditioner service manual 105 3 ASW H12A4 ET Indoor unit exploded picture ...
Страница 110: ...AUX air conditioner service manual 107 Outdoor unit exploded picture ...
Страница 112: ...AUX air conditioner service manual 109 4 ASW H12A4 EC Indoor unit exploded picture ...
Страница 114: ...AUX air conditioner service manual 111 Outdoor unit exploded picture ...
Страница 116: ...AUX air conditioner service manual 113 5 ASW H18B4 ET Indoor unit exploded picture ...
Страница 118: ...AUX air conditioner service manual 115 Outdoor unit exploded picture ...
Страница 120: ...AUX air conditioner service manual 117 6 ASW H24B4 ET Indoor unit exploded picture ...
Страница 122: ...AUX air conditioner service manual 119 Outdoor unit exploded picture ...
Страница 124: ...AUX air conditioner service manual 121 Section two H series products 1 ASW H09A4 HSF Indoor unit exploded picture ...
Страница 126: ...AUX air conditioner service manual 123 Outdoor unit exploded picture ...
Страница 128: ...AUX air conditioner service manual 125 2 ASW H09A4 HSL Indoor unit exploded picture ...
Страница 130: ...AUX air conditioner service manual 127 Outdoor unit exploded picture ...
Страница 132: ...AUX air conditioner service manual 129 3 ASW H09A4 HS Indoor unit exploded picture ...
Страница 134: ...AUX air conditioner service manual 131 Outdoor unit exploded picture ...
Страница 136: ...AUX air conditioner service manual 133 4 ASW H18B4 HS Indoor unit exploded picture ...
Страница 138: ...AUX air conditioner service manual 135 Outdoor unit exploded picture ...
Страница 140: ...AUX air conditioner service manual 137 5 ASW H24B4 HS Indoor unit exploded picture ...
Страница 142: ...AUX air conditioner service manual 139 Outdoor unit exploded picture ...
Страница 146: ...AUX air conditioner service manual 143 Outdoor unit exploded picture ...
Страница 148: ...AUX air conditioner service manual 145 2 ASF H41A5 C Indoor unit exploded picture ...
Страница 149: ...AUX air conditioner service manual 146 ...
Страница 151: ...AUX air conditioner service manual 148 Outdoor unit exploded picture ...
Страница 166: ...AUX air conditioner service manual 163 ...
Страница 240: ......