AUX air conditioner service manual
215
tube and sheet-metal. We should install damp piece or insulation sleeve.
⑶
Vibration of compressor causes collision between copper tubes. Install insulation to isolate two
tubes.
In such case, we should explain to client that it’s not air conditioner fault, it is caused by improper
installation and can be handled easily.
Case 9: Outdoor fan motor bracket deformed because of the vibrating
Unit Model: ASW-12A4/HY
Phenomena
:
Outdoor unit made loud noise in operation
Cause Analysis: air conditioner buzzed when it was in cooling mode. Maintenance personnel judged
that sound was made by outdoor unit. Opened outdoor shell, checked the internal tubes and
compressor and found that they operated normally. So maintenance personnel suspected noise was
made by outdoor fan. Turned off compressor, noise was still very loud. Changed fan motor, but noise
remained the same. Check carefully and found that fan motor bracket bent; adjusted the bracket
vertically, installed fan again, and run the air conditioner, buzz was eliminated.
Solution: adjusted outdoor fan
Experience Conclusion: to reduce noise, more attention shall be paid to stability of auxiliary support
and fasteners and whether they have deformed.
Case 10: Outdoor grille collided with front panel
Unit Model : ASW-H07B4/Y
Phenomena
:
Outdoor unit made loud noise
Cause Analysis: according to client, outdoor unit made loud noise. We checked outdoor unit and it was
installed properly, its shell was also quite normal. Touched the cover of outdoor unit, noise was
reduced, but not eliminated and outdoor grille made slight quaver. Compacted or pulled out this grille,
noise was eliminated. Checked carefully and found that plastic clip between grille and front panel
hadn’t been fastened tightly and made noise.
Solution: filled small plastic cushion between outdoor grille and front panel and avoided impacting the
appearance of the outdoor unit.
Experience Conclusion: compared to indoor unit noise, outdoor unit noise can be eliminated easily,
the most important thing is to find out the right orientation and handle the problem smartly.
Case 11: Noise caused by blocking of indoor separate capillary
Unit Model: ASW-H24B4
Phenomena: Outdoor unit made loud noise and cooling and heating efficiency was unsatisfactory.
Cause Analysis: indoor unit produced air-stream sound, temperature difference of air outlet was only
7 Celsius Degree and low pressure was 0.3 MPa, both data were relatively low; high pressure tube was
over-cold, and compressor was easy to change to over-heat protection mode. Broke off compressor,
noise disappeared; broke off indoor fan, refrigerant made loud noise, so maintenance personnel judged
that noise was caused by flow throttling. Touched branches of evaporator, and found that temperature
Содержание E Series
Страница 1: ......
Страница 32: ...AUX air conditioner service manual The other parts 29 ...
Страница 33: ...AUX air conditioner service manual 30 ...
Страница 102: ...AUX air conditioner service manual 99 Outdoor unit exploded picture ...
Страница 104: ...AUX air conditioner service manual 101 2 ASW H09A4 EC Indoor unit exploded picture ...
Страница 106: ...AUX air conditioner service manual 103 Outdoor unit exploded picture ...
Страница 108: ...AUX air conditioner service manual 105 3 ASW H12A4 ET Indoor unit exploded picture ...
Страница 110: ...AUX air conditioner service manual 107 Outdoor unit exploded picture ...
Страница 112: ...AUX air conditioner service manual 109 4 ASW H12A4 EC Indoor unit exploded picture ...
Страница 114: ...AUX air conditioner service manual 111 Outdoor unit exploded picture ...
Страница 116: ...AUX air conditioner service manual 113 5 ASW H18B4 ET Indoor unit exploded picture ...
Страница 118: ...AUX air conditioner service manual 115 Outdoor unit exploded picture ...
Страница 120: ...AUX air conditioner service manual 117 6 ASW H24B4 ET Indoor unit exploded picture ...
Страница 122: ...AUX air conditioner service manual 119 Outdoor unit exploded picture ...
Страница 124: ...AUX air conditioner service manual 121 Section two H series products 1 ASW H09A4 HSF Indoor unit exploded picture ...
Страница 126: ...AUX air conditioner service manual 123 Outdoor unit exploded picture ...
Страница 128: ...AUX air conditioner service manual 125 2 ASW H09A4 HSL Indoor unit exploded picture ...
Страница 130: ...AUX air conditioner service manual 127 Outdoor unit exploded picture ...
Страница 132: ...AUX air conditioner service manual 129 3 ASW H09A4 HS Indoor unit exploded picture ...
Страница 134: ...AUX air conditioner service manual 131 Outdoor unit exploded picture ...
Страница 136: ...AUX air conditioner service manual 133 4 ASW H18B4 HS Indoor unit exploded picture ...
Страница 138: ...AUX air conditioner service manual 135 Outdoor unit exploded picture ...
Страница 140: ...AUX air conditioner service manual 137 5 ASW H24B4 HS Indoor unit exploded picture ...
Страница 142: ...AUX air conditioner service manual 139 Outdoor unit exploded picture ...
Страница 146: ...AUX air conditioner service manual 143 Outdoor unit exploded picture ...
Страница 148: ...AUX air conditioner service manual 145 2 ASF H41A5 C Indoor unit exploded picture ...
Страница 149: ...AUX air conditioner service manual 146 ...
Страница 151: ...AUX air conditioner service manual 148 Outdoor unit exploded picture ...
Страница 166: ...AUX air conditioner service manual 163 ...
Страница 240: ......