of two back branches was obviously lower, so system was blocked when it was welded. Released
refrigerant, welded the system again and fault was eliminated.
Solution: welded the copper tube again, air conditioner run normally
Experience Conclusion: generally, air-stream sound was produced by over throttling, so we shall
analyze causes for throttling.
Case 12: Noise caused by bending of connection pipe
Unit Model: ASW-H12A4/M
Phenomena
:
Indoor unit made loud noise
Cause Analysis: opened the indoor unit and checked all components, we found that when compressor
run, it made noise, so air duct, motor and other components had no problem. We checked the
components of evaporator and listened to the sound and then found that noise was made by evaporator.
Gas pipe pressure was relatively lower than normal value; we continued to check and found that
connection pipe between indoor and outdoor units was folded badly.
Solution: after we replaced deformed part of connection pipe, the foregoing faults disappeared.
Experience Conclusion: only when air conditioner is in cooling and heating modes can noise be heard,
so gas pipe, motor and components have no problems. Check the system carefully, whistle is from
evaporator, which has been blocked with dirt and ice or blocked when the tube is welded. Decide the
fault position through listening, visual check and measuring temperature difference, and then deal with
the faults accordingly.
Case 13: Noise caused by improper installation
Unit Model: ASW-H12A4/ED
Phenomena
:
Abnormal noise could be heard after the air conditioner was turned on and run for some
time.
Cause Analysis: according to client, “coo” could be heard occasionally. Maintenance personnel
checked the air conditioner for about 3 hours, “coo” could be heard sometimes, we believed it was
from water collection pan in indoor unit when air condition was in cooling mode, and water drain pipe
might have some obstacles. We checked the pipe from indoor unit to outdoor unit carefully, and found
that water drain pipe in indoor unit was tied too tightly, and water couldn’t flow smoothly; water line
outside had a U type bending, so we considered that air flow returned sometimes and produced
abnormal sound. Because water pipe was not flat completely, water could still be drained and indoor
unit didn’t leak, it was very difficult to find the problem. We wrapped water pipe again, and adjusted
water pipe of outdoor unit, and then air conditioner could operate properly.
Solution: adjusted water drain pipe
Experience Conclusion: to deal with such kind of strange problems, maintenance personnel shall be
patient to check and consider in various aspects.
Case 14: Noise caused by improper outdoor unit installation
Содержание E Series
Страница 1: ......
Страница 32: ...AUX air conditioner service manual The other parts 29 ...
Страница 33: ...AUX air conditioner service manual 30 ...
Страница 102: ...AUX air conditioner service manual 99 Outdoor unit exploded picture ...
Страница 104: ...AUX air conditioner service manual 101 2 ASW H09A4 EC Indoor unit exploded picture ...
Страница 106: ...AUX air conditioner service manual 103 Outdoor unit exploded picture ...
Страница 108: ...AUX air conditioner service manual 105 3 ASW H12A4 ET Indoor unit exploded picture ...
Страница 110: ...AUX air conditioner service manual 107 Outdoor unit exploded picture ...
Страница 112: ...AUX air conditioner service manual 109 4 ASW H12A4 EC Indoor unit exploded picture ...
Страница 114: ...AUX air conditioner service manual 111 Outdoor unit exploded picture ...
Страница 116: ...AUX air conditioner service manual 113 5 ASW H18B4 ET Indoor unit exploded picture ...
Страница 118: ...AUX air conditioner service manual 115 Outdoor unit exploded picture ...
Страница 120: ...AUX air conditioner service manual 117 6 ASW H24B4 ET Indoor unit exploded picture ...
Страница 122: ...AUX air conditioner service manual 119 Outdoor unit exploded picture ...
Страница 124: ...AUX air conditioner service manual 121 Section two H series products 1 ASW H09A4 HSF Indoor unit exploded picture ...
Страница 126: ...AUX air conditioner service manual 123 Outdoor unit exploded picture ...
Страница 128: ...AUX air conditioner service manual 125 2 ASW H09A4 HSL Indoor unit exploded picture ...
Страница 130: ...AUX air conditioner service manual 127 Outdoor unit exploded picture ...
Страница 132: ...AUX air conditioner service manual 129 3 ASW H09A4 HS Indoor unit exploded picture ...
Страница 134: ...AUX air conditioner service manual 131 Outdoor unit exploded picture ...
Страница 136: ...AUX air conditioner service manual 133 4 ASW H18B4 HS Indoor unit exploded picture ...
Страница 138: ...AUX air conditioner service manual 135 Outdoor unit exploded picture ...
Страница 140: ...AUX air conditioner service manual 137 5 ASW H24B4 HS Indoor unit exploded picture ...
Страница 142: ...AUX air conditioner service manual 139 Outdoor unit exploded picture ...
Страница 146: ...AUX air conditioner service manual 143 Outdoor unit exploded picture ...
Страница 148: ...AUX air conditioner service manual 145 2 ASF H41A5 C Indoor unit exploded picture ...
Страница 149: ...AUX air conditioner service manual 146 ...
Страница 151: ...AUX air conditioner service manual 148 Outdoor unit exploded picture ...
Страница 166: ...AUX air conditioner service manual 163 ...
Страница 240: ......