AUX air conditioner service manual
187
a
、
Commute, demodulation, switch and stabilivolt diode. Remove diode from electrical panel, check its
single phase conductivity with R×1K and R×100 of universal meter. Check method: contact two ends
of diode with two handles of meter, record the resistance value, then change two handles with each
other and measure again. For a normal diode, two resistance values are different greatly; large one is
called reverse resistance and the smaller one forward resistance. Normally, forward resistance of
silicon diode is several hundreds or thousands ohm, and reverse resistance can be 1 1M
Ω
; for
germanium diode, forward resistances is 0~1000
Ω
, while reverse resistance over 100K
Ω
. If reverse
resistance is very low, this diode has been broken; if both reverse and forward resistances are
∞
, diode
has broken; If difference between reverse and forward resistances is very slight or any of the two
resistances deviates greatly from normal value, this diode is defective and shall be replaced. However,
the said standard doesn’t apply to some special diodes, for example, high-voltage silicon stack,
(forward resistance of which is also very large, index finger only moves slightly even in the R×10K of
universal meter), and some stabilivolt tubes (reverse resistance around 20K
Ω
).
b
、
Light-emitting diode(LED). Except low voltage types, forward conductive voltage is larger than
1.8V, while most universal meters are of a voltage of 1.5V(except for R×10K), so they are unable to
make diode conduct, which cause reverse and forward resistances very large or even infinitely great.
To check LED, R×10K or universal meters with 9V or over voltage shall be used. When we use
R×10K of universal meter, LED can be checked in the same way as normal diode. No matter what
kind of diode, positive and negative poles can be judged. When you measure reverse resistance, the
end touched by red handle is positive pole, the other end is negative pole.
②
Performance check for common triode
Main parameters to be measured are Iceo and h
FE
. In general, actual-measured resistance of
germanium triode with middle-small power shall be over 10~20K
Ω
; resistance of silicon triode shall
be over 100K
Ω
, and actually-measured value is infinitely great, i.e. index finger doesn’t swing. If
actual resistance is excess slight, it shows that Iceo is very large, and this kind of triodes can not be
used for their poor capacity. If actual resistance nears zero, c and e poles triode has broken down.
ICBO can also be measured in the same way: touch two handles of universal meter on b and c poles to
measure reverse resistance between them. Normally, resistance of germanium triode is larger than that
we obtain when we measure Iceo, and resistance of silicon triode is infinite great.
Based on the situation of measuring I
ceo,
another 100K
Ω
resistance(silicon triode) or 20K
Ω
resistance(germanium) shall be connected to b and c poles. The more value indicated by index finger
becomes small, and the more h
FE
is large; if resistance doesn’t change much or changes slightly, triode
is broken or its enlargement capacity is very poor. Also, you can touch b and c with wet hands, but
avoiding direct touch of b and c, to measure the resistance. In addition, most universal meters
produced in recent years have position to measure h
FE
of small power triode. Operation method: turn
resistance position to 0
Ω
, and then turn to h
FE
position
;
Insert handles to related test hole, and read the
enlargement coefficient from h
FE
rule directly.
5. Cases of Maintenance of Electrical Control System
Case 1 Silicon Control is broken and indoor unit creates noise
Product Model
:
ASW-H07B4/HA
Phenomena
:
When unit is switched off, indoor fan runs slowly, and when it is turned on, unpleasant
Содержание E Series
Страница 1: ......
Страница 32: ...AUX air conditioner service manual The other parts 29 ...
Страница 33: ...AUX air conditioner service manual 30 ...
Страница 102: ...AUX air conditioner service manual 99 Outdoor unit exploded picture ...
Страница 104: ...AUX air conditioner service manual 101 2 ASW H09A4 EC Indoor unit exploded picture ...
Страница 106: ...AUX air conditioner service manual 103 Outdoor unit exploded picture ...
Страница 108: ...AUX air conditioner service manual 105 3 ASW H12A4 ET Indoor unit exploded picture ...
Страница 110: ...AUX air conditioner service manual 107 Outdoor unit exploded picture ...
Страница 112: ...AUX air conditioner service manual 109 4 ASW H12A4 EC Indoor unit exploded picture ...
Страница 114: ...AUX air conditioner service manual 111 Outdoor unit exploded picture ...
Страница 116: ...AUX air conditioner service manual 113 5 ASW H18B4 ET Indoor unit exploded picture ...
Страница 118: ...AUX air conditioner service manual 115 Outdoor unit exploded picture ...
Страница 120: ...AUX air conditioner service manual 117 6 ASW H24B4 ET Indoor unit exploded picture ...
Страница 122: ...AUX air conditioner service manual 119 Outdoor unit exploded picture ...
Страница 124: ...AUX air conditioner service manual 121 Section two H series products 1 ASW H09A4 HSF Indoor unit exploded picture ...
Страница 126: ...AUX air conditioner service manual 123 Outdoor unit exploded picture ...
Страница 128: ...AUX air conditioner service manual 125 2 ASW H09A4 HSL Indoor unit exploded picture ...
Страница 130: ...AUX air conditioner service manual 127 Outdoor unit exploded picture ...
Страница 132: ...AUX air conditioner service manual 129 3 ASW H09A4 HS Indoor unit exploded picture ...
Страница 134: ...AUX air conditioner service manual 131 Outdoor unit exploded picture ...
Страница 136: ...AUX air conditioner service manual 133 4 ASW H18B4 HS Indoor unit exploded picture ...
Страница 138: ...AUX air conditioner service manual 135 Outdoor unit exploded picture ...
Страница 140: ...AUX air conditioner service manual 137 5 ASW H24B4 HS Indoor unit exploded picture ...
Страница 142: ...AUX air conditioner service manual 139 Outdoor unit exploded picture ...
Страница 146: ...AUX air conditioner service manual 143 Outdoor unit exploded picture ...
Страница 148: ...AUX air conditioner service manual 145 2 ASF H41A5 C Indoor unit exploded picture ...
Страница 149: ...AUX air conditioner service manual 146 ...
Страница 151: ...AUX air conditioner service manual 148 Outdoor unit exploded picture ...
Страница 166: ...AUX air conditioner service manual 163 ...
Страница 240: ......