AUX air conditioner service manual
33
protection), the wind speed of the indoor fan is high wind, the running mode is cooling mode, and the
wind door is maximum opening.
b) There are no anti-freezing protection and high temperature-preventing protection during trial
operation.
⑶
Automatic run mode
When controller select an automatic working mode, the indication light twinkles for 20 seconds and
the air-conditioner does not start working until the working mode to be selected by the system; The
air-conditioner automatically selects one of the cooling, dehumidification, and heating mode as the
working mode according to the indoor air temperature .
①
When TA
≥
TA1, the controller enters into the cooling mode and follows the mode in working. The
setting temperature herein is 24
℃
and the air-conditioner runs according to the setting wind speed;
②
When TA2<TA<TA1, the controller enters into the dehumidification mode and follows the mode
in working. The setting temperature is 24
℃
and the air-conditioner runs according to the setting
wind speed;
③
When TA
≤
TA2, the controller enters into the heating mode and follows the mode in working (The
cooling only type follows the ventilation mode). The setting temperature herein is 24
℃
and the
air-conditioner runs according to the setting wind speed;
④
This mode includes the functions of timing, sleeping, auto-restart (optional), negative ion
(optional), I feel
(
optional
)
;
⑤
The system mode will not change along with the variety of the indoor temperature after being
selected. The new working mode will be selected again after air-conditioner turns off or mode switch.
⑷
Cooling mode
The setting temperature shall be set by the remote control. The temperature controlling range is 16
℃
-
32
℃
. The setting temperature can be adjusted through the button of “+” “-”. The setting wind speed
can be adjusted through the button of “wind speed selection” in the selection of the four wind speed
types, such as strong wind, high wind, low wind and mute wind. The four-way valve always be closed
under this mode. The other action is as following:
①
When TA - TS
≥
1
℃,
after the compressor meet the 3 minutes delay protection, the compressor and
the outdoor fan start running;
②
When TA = TS
,
maintain the previous status;
③
When TA - TS
≤
-1
℃,
after the compressor meet the 3 minutes protection condition, the compressor
and the outdoor fan turn off;
④
The setting wind speed can be adjusted by the remote control during the ongoing cooling process,
and the interior fan still retains working;
⑤
When the status of TE
≤
TE1 last for 10 seconds and the compressor keeps working for above
than 5 minutes, turn off the compressor and outdoor fan, the indoor fan keep working according to the
setting wind speed; quit from such protection if TE
≥
7
℃
;
⑥
This mode includes the functions of timing, sleeping, auto-restart (optional), negative ion
(optional), I feel
(
optional
)
;
⑦
When the cooling ongoing
,
the button of the “Swing” can control the swing and stop of the
horizontal air-blade;
Содержание E Series
Страница 1: ......
Страница 32: ...AUX air conditioner service manual The other parts 29 ...
Страница 33: ...AUX air conditioner service manual 30 ...
Страница 102: ...AUX air conditioner service manual 99 Outdoor unit exploded picture ...
Страница 104: ...AUX air conditioner service manual 101 2 ASW H09A4 EC Indoor unit exploded picture ...
Страница 106: ...AUX air conditioner service manual 103 Outdoor unit exploded picture ...
Страница 108: ...AUX air conditioner service manual 105 3 ASW H12A4 ET Indoor unit exploded picture ...
Страница 110: ...AUX air conditioner service manual 107 Outdoor unit exploded picture ...
Страница 112: ...AUX air conditioner service manual 109 4 ASW H12A4 EC Indoor unit exploded picture ...
Страница 114: ...AUX air conditioner service manual 111 Outdoor unit exploded picture ...
Страница 116: ...AUX air conditioner service manual 113 5 ASW H18B4 ET Indoor unit exploded picture ...
Страница 118: ...AUX air conditioner service manual 115 Outdoor unit exploded picture ...
Страница 120: ...AUX air conditioner service manual 117 6 ASW H24B4 ET Indoor unit exploded picture ...
Страница 122: ...AUX air conditioner service manual 119 Outdoor unit exploded picture ...
Страница 124: ...AUX air conditioner service manual 121 Section two H series products 1 ASW H09A4 HSF Indoor unit exploded picture ...
Страница 126: ...AUX air conditioner service manual 123 Outdoor unit exploded picture ...
Страница 128: ...AUX air conditioner service manual 125 2 ASW H09A4 HSL Indoor unit exploded picture ...
Страница 130: ...AUX air conditioner service manual 127 Outdoor unit exploded picture ...
Страница 132: ...AUX air conditioner service manual 129 3 ASW H09A4 HS Indoor unit exploded picture ...
Страница 134: ...AUX air conditioner service manual 131 Outdoor unit exploded picture ...
Страница 136: ...AUX air conditioner service manual 133 4 ASW H18B4 HS Indoor unit exploded picture ...
Страница 138: ...AUX air conditioner service manual 135 Outdoor unit exploded picture ...
Страница 140: ...AUX air conditioner service manual 137 5 ASW H24B4 HS Indoor unit exploded picture ...
Страница 142: ...AUX air conditioner service manual 139 Outdoor unit exploded picture ...
Страница 146: ...AUX air conditioner service manual 143 Outdoor unit exploded picture ...
Страница 148: ...AUX air conditioner service manual 145 2 ASF H41A5 C Indoor unit exploded picture ...
Страница 149: ...AUX air conditioner service manual 146 ...
Страница 151: ...AUX air conditioner service manual 148 Outdoor unit exploded picture ...
Страница 166: ...AUX air conditioner service manual 163 ...
Страница 240: ......