AUX air conditioner service manual
226
The “running” light and “swing” light are twinkling and last for 0.5/0.5 second, the other indication
lights are invariable, and the system turns off.
4. ASF-H24B4/B, ASF-H41A5/B faults display and protection display:
⑴
Fault of the Indoor temperature sensor
:
System turns off; the panel displays “E1”
⑵
The fault of the outdoor tube temperature sensor on the indoor panel
:
System doesn’t turn off; the panel displays“E2”.
⑶
Fault of the interior tube temperature sensor
:
System doesn’t turn off, the panel display “E3”
,
runs under the mode without interior temperature
sensor
:
When under the heating mode, there is no overheating protection, anti-cooling wind protection
and residual heat removal function, the indoor fan starts running at the setting fan speed 30 seconds
later after the compressor’s starting, and stops after 30 seconds running at the ultra low fan speed
without compressor; When under the refrigeration mode, there is no anti-freezing protection.
⑷
Communication fault
:
The system turns off or can’t start, the panel displays “E4”
,
which may be displayed under either on or
off status.
⑸
The protection of outdoor reverse phase and failure of phase:
System stops, and the panel displays “E6”
⑹
Heating and defrosting
:
The “defrosting” indication light on the panel is twinkling, (0.5/0.5) the other are invariable.
⑺
When the indoor tube temperature available, the indoor refrigeration anti-freezing protection
:
The “running” light and “cooling” light on the panel are twinkling (0.5/0.5), the other are invariable.
⑻
When the indoor tube temperature available, the indoor heating overheating protection
:
The “running” light and “heating” light on the panel are twinkling (0.5/0.5), the other are invariable.
⑼
When the indoor tube temperature available, the indoor heating long time anti-cooling wind
protection
:
The “running” light on the panel is twinkling (0.5/0.5), the other are invariable.
5
、
ASW-(H)18A4/III fault display and protection display
⑴
Damage to the outdoor coil pipe
:
The timing light on the panel twinkles one time/second.
⑵
The damage to the indoor temperature sensor
:
The timing light on the panel twinkles one time/8 seconds.
⑶
The damage to the indoor coil pipe sensor
:
The timing light on the panel twinkles two times/8 seconds.
⑷
Heating and defrosting
The sleeping light twinkles (0.5/0.5 second
)
⑸
Refrigerating anti-freezing protection
:
The operation light and the timing light of the panel twinkle (0.5/0.5 second
)
6
、
Heating anti-overheating protection
:
The “running” light and “sleeping” light are twinkling
(
0.5/0.5second
)
⑺
Heating long time anti-cooling wind protection
:
The “running” light is twinkling
(
0.5/0.5second
)
6
、
FS(Y)
、
DS(Y)
、
ZVY
、
CSY model air-conditioner faults display and protection display
Содержание E Series
Страница 1: ......
Страница 32: ...AUX air conditioner service manual The other parts 29 ...
Страница 33: ...AUX air conditioner service manual 30 ...
Страница 102: ...AUX air conditioner service manual 99 Outdoor unit exploded picture ...
Страница 104: ...AUX air conditioner service manual 101 2 ASW H09A4 EC Indoor unit exploded picture ...
Страница 106: ...AUX air conditioner service manual 103 Outdoor unit exploded picture ...
Страница 108: ...AUX air conditioner service manual 105 3 ASW H12A4 ET Indoor unit exploded picture ...
Страница 110: ...AUX air conditioner service manual 107 Outdoor unit exploded picture ...
Страница 112: ...AUX air conditioner service manual 109 4 ASW H12A4 EC Indoor unit exploded picture ...
Страница 114: ...AUX air conditioner service manual 111 Outdoor unit exploded picture ...
Страница 116: ...AUX air conditioner service manual 113 5 ASW H18B4 ET Indoor unit exploded picture ...
Страница 118: ...AUX air conditioner service manual 115 Outdoor unit exploded picture ...
Страница 120: ...AUX air conditioner service manual 117 6 ASW H24B4 ET Indoor unit exploded picture ...
Страница 122: ...AUX air conditioner service manual 119 Outdoor unit exploded picture ...
Страница 124: ...AUX air conditioner service manual 121 Section two H series products 1 ASW H09A4 HSF Indoor unit exploded picture ...
Страница 126: ...AUX air conditioner service manual 123 Outdoor unit exploded picture ...
Страница 128: ...AUX air conditioner service manual 125 2 ASW H09A4 HSL Indoor unit exploded picture ...
Страница 130: ...AUX air conditioner service manual 127 Outdoor unit exploded picture ...
Страница 132: ...AUX air conditioner service manual 129 3 ASW H09A4 HS Indoor unit exploded picture ...
Страница 134: ...AUX air conditioner service manual 131 Outdoor unit exploded picture ...
Страница 136: ...AUX air conditioner service manual 133 4 ASW H18B4 HS Indoor unit exploded picture ...
Страница 138: ...AUX air conditioner service manual 135 Outdoor unit exploded picture ...
Страница 140: ...AUX air conditioner service manual 137 5 ASW H24B4 HS Indoor unit exploded picture ...
Страница 142: ...AUX air conditioner service manual 139 Outdoor unit exploded picture ...
Страница 146: ...AUX air conditioner service manual 143 Outdoor unit exploded picture ...
Страница 148: ...AUX air conditioner service manual 145 2 ASF H41A5 C Indoor unit exploded picture ...
Страница 149: ...AUX air conditioner service manual 146 ...
Страница 151: ...AUX air conditioner service manual 148 Outdoor unit exploded picture ...
Страница 166: ...AUX air conditioner service manual 163 ...
Страница 240: ......