AUX air conditioner service manual
206
condenser, so refrigerant leaked out.
Solution: repair-welded leak source and added refrigerant
Experience Conclusion: when air conditioner is running, system pressure is zero, we can judge that
refrigerant leaks out; generally, oil stain can be seen on leak sources. Maintenance personnel shall be
familiar with blinking conditions of indicator.
Case 10 Weld of U type tube of condenser leaked
Unit Model
:
ASW-H12B4/HY
Phenomena: failed to cool
Cause Analysis: air conditioner was used less than one month, cooling efficiency was unsatisfactory.
Checked the air conditioner, temperature of compressor was relatively high; current was 3A, low
pressure was 3kg, outdoor fan run normally. We presumed that system was blocked, leaked or return
gas and discharge capacity of compressor was quite unsatisfactory. We brought air conditioner to
Maintenance Office, purged the system with nitrogen, checked leak sources under high pressure and
found that weld of U type tube under condenser leaked.
Solution: repair-welded, vacuum the system and filled the system with refrigerant.
Experience Conclusion: air conditioner has been used for a short time, but refrigerating efficiency is
unsatisfactory, in most cases, system leaks, so firstly we shall check leak source.
Case 11 Four-way valve was broken
Unit Model
:
ASF-H24B4
Phenomena
:
Air conditioner produced heat once it was started up.
Cause Analysis: once we turned on the air conditioner, it worked in heating mode. It was a new
appliance, so we presumed that four-way valve had some problems. We checked circuit, and it was
connected correctly; coil resistance of four-way valve was normal and conducted electricity well, so
four-way valve was blocked: because it was a new appliance, there’s very low chance that four-way
valve was broken. We knocked the four-way valve and started the air conditioner repeatedly; it still
failed to work properly. So finally we confirmed that four-way valve was broken.
Solution: replace four-way valve
Experience Conclusion: don’t replace four-way valve easily, slightly blocked phenomena can be fixed
by simply physical method, especially for the appliance used for a short time.
Case 12 the retaining valve was broken
Unit Model
:
ASW-H18A4/ III
Phenomena: Poor cooling efficiency
Cause Analysis: voltage of client’s house was 220v. According to client, room was not cooled down
although air conditioner had worked for some time. We checked the air conditioner, low pressure was
0.65Mpa, being relatively high. We released refrigerant until the pressure was 0.55Mpa, cold wind
from outlet of indoor unit was weak, and work current was 7.3A, which was normal. We touched high
and low pressure copper tubes, low pressure tube became colder, but high pressure tube was not cold,
so there’s no failure in compressor. At that time, pressure increased to 0.36Mpa, we touched 4 copper
Содержание E Series
Страница 1: ......
Страница 32: ...AUX air conditioner service manual The other parts 29 ...
Страница 33: ...AUX air conditioner service manual 30 ...
Страница 102: ...AUX air conditioner service manual 99 Outdoor unit exploded picture ...
Страница 104: ...AUX air conditioner service manual 101 2 ASW H09A4 EC Indoor unit exploded picture ...
Страница 106: ...AUX air conditioner service manual 103 Outdoor unit exploded picture ...
Страница 108: ...AUX air conditioner service manual 105 3 ASW H12A4 ET Indoor unit exploded picture ...
Страница 110: ...AUX air conditioner service manual 107 Outdoor unit exploded picture ...
Страница 112: ...AUX air conditioner service manual 109 4 ASW H12A4 EC Indoor unit exploded picture ...
Страница 114: ...AUX air conditioner service manual 111 Outdoor unit exploded picture ...
Страница 116: ...AUX air conditioner service manual 113 5 ASW H18B4 ET Indoor unit exploded picture ...
Страница 118: ...AUX air conditioner service manual 115 Outdoor unit exploded picture ...
Страница 120: ...AUX air conditioner service manual 117 6 ASW H24B4 ET Indoor unit exploded picture ...
Страница 122: ...AUX air conditioner service manual 119 Outdoor unit exploded picture ...
Страница 124: ...AUX air conditioner service manual 121 Section two H series products 1 ASW H09A4 HSF Indoor unit exploded picture ...
Страница 126: ...AUX air conditioner service manual 123 Outdoor unit exploded picture ...
Страница 128: ...AUX air conditioner service manual 125 2 ASW H09A4 HSL Indoor unit exploded picture ...
Страница 130: ...AUX air conditioner service manual 127 Outdoor unit exploded picture ...
Страница 132: ...AUX air conditioner service manual 129 3 ASW H09A4 HS Indoor unit exploded picture ...
Страница 134: ...AUX air conditioner service manual 131 Outdoor unit exploded picture ...
Страница 136: ...AUX air conditioner service manual 133 4 ASW H18B4 HS Indoor unit exploded picture ...
Страница 138: ...AUX air conditioner service manual 135 Outdoor unit exploded picture ...
Страница 140: ...AUX air conditioner service manual 137 5 ASW H24B4 HS Indoor unit exploded picture ...
Страница 142: ...AUX air conditioner service manual 139 Outdoor unit exploded picture ...
Страница 146: ...AUX air conditioner service manual 143 Outdoor unit exploded picture ...
Страница 148: ...AUX air conditioner service manual 145 2 ASF H41A5 C Indoor unit exploded picture ...
Страница 149: ...AUX air conditioner service manual 146 ...
Страница 151: ...AUX air conditioner service manual 148 Outdoor unit exploded picture ...
Страница 166: ...AUX air conditioner service manual 163 ...
Страница 240: ......