DL205 Analog Manual, 7th Edition Rev. D
13-17
Chapter 13: F2-02DAS-2, 0-5V, 0-10V, 2-Channel Isolated Analog Output
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
b
C
D
Analog and Digital Value Conversions
It is sometimes useful to do quick conversions between the signal levels and the digital values.
This can be helpful during startup and/or troubleshooting. The following table shows some
formulas to help with the conversions.
For example, if a 4V signal is needed, use the
formula to the right to determine the digital value
to be stored in the V-memory location which is
designated to store the data.
Range
If the digital value is known
If the analog signal level is known.
0–5 VDC
A = 5D
65535
D = 65535 A
5
0–10 VDC
A = 10D
65535
D = 65535 A
10
D = 65535 A
5
D = 65535 (4)
5
D = (13107) (4)
D = 52428 (CCCC