DL205 Analog Manual, 7th Edition Rev. D
10-8
Chapter 10: F2-08DA-1, 8-Channel Analog Current Output
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Channel Scanning Sequence for DL240, DL250-1, and DL260 CPUs
(Pointer Method)
If either a DL240, DL250-1 or a DL260 CPU is used, all channels can be updated on every
scan. This is because the all three CPUs support special V-memory locations that are used to
manage the data transfer. This is discussed in more detail in the next section on
Writing the
Control Program
.
Understanding the Output Assignments
Remember that the F2-08DA-1 module appears to the CPU as a 16-point discrete output
module. These points provide the data value and an indication of which channel to update.
Note, if either a DL240, DL250 or a DL260 CPU is being used, these bits may never have to
be used, but it may be an aid to help understand the data format.
Since all output points are automatically mapped into V-memory, the location of the data
word that will be assigned to the module can be simply determined.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
b
C
D
Channel 1, 2...8
Channel 1, 2...8
Channel 1, 2...8
Channel 1, 2...8
Scan N
Calculate the data
Write data
Read inputs
Execute Application Program
Scan N+1
Scan N+2
Scan N+3
Scan N+4
Scan
Write to outputs
System With
DL240/250--1/260
CPU Using Point-
er Method
Channel 1, 2...8