DL205 Analog Manual, 7th Edition Rev. D
7-2
Chapter 7: F2-04THM, 4-Channel Thermocouple Input
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
B
C
D
Module Specifications
The F2-04THM, 4-Channel Thermocouple Input Module
provides the following features and benefits:
•
Four thermocouple input channels with 16-bit voltage
resolution or 0.1°F/°C temperature resolution.
•
Automatically converts type E, J, K, R, S, T, B, N, or C
thermocouple signals into direct temperature readings. No
extra scaling or complex conversion is required.
•
Temperature data can be expressed in °F or °C.
• Module can be configured as ±5V, ±156mV, 0–5V,
0–156mV input and will convert volts and millivolt signal
levels into 16-bit digital (0–65535) values.
•
Signal processing features include automatic cold junction
compensation, thermocouple linearization, and digital
filtering.
•
The temperature calculation and linearization are based on
data provided by the National Institute of Standards and
Technology (NIST).
•
Diagnostic features include detection of thermocouple
burnout or disconnection.
The following tables provide the specifications for the F2-04THM Analog Input Module.
Review these specifications to make sure the module meets your application requirements.
One count in the specification table is equal to one least significant bit of the analog data value
(1 in 65535).
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
b
C
D
CH1 +
CH1
CH2 +
CH2
CH3 +
CH3
CH4 +
CH4
+24V
0v
IN
F2-04THM
TEMP
VOLT
THERMOCOUPLE mV
0-5, -5-+5VDC
18-26.4VDC, 60mA
General Specifications
Number of Channels
4, differential
Common Mode Range
±5VDC
Common Mode Rejection
90 dB min. @ DC, 150 dB min. @ 50/60Hz.
Input Impedance
1M
q
min.
Absolute Maximum Ratings
Fault-protected inputs to ±50VDC
Accuracy vs. Temperature
±5ppm/ºC maximum; full scale calibration
(including maximum offset change)
PLC Update Rate
4 channels per scan max. DL240/250–1/260 CPU
1 channel per scan ,max. DL230 CPU
Digital Inputs
Input Points Required
16 binary data bits, 2 channel ID bits, 4 diagnostic bits
32 point (X) input module
Power Budget Requirement
110mA maximum, 18–26.4 VDC
Operating Temperature
0–60ºC (32–140ºF)
Storage Temperature
-2–70ºC (-4–158ºF)
Relative Humidity
5–95% (non-condensing)
Environmental air
No corrosive gases permitted
Vibration
MIL STD 810C 514.2
Shock
MIL STD 810C 516.2
Noise Immunity
NEMA ICS3-304