Sending Data to One Channel
If more than one channel is used, or if updates are to be controlled separately, the following
program can be used.
Analog and Digital Value Conversions
It is sometimes useful to do quick conversions between the signal levels and the digital values.
This can be helpful during startup or troubleshooting. The following table shows some
formulas help with the conversions.
For example, to covert a 10mA signal level to a
digital value, substitute 10 for A and complete
the math as shown in the example to the right.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
b
C
D
BIN
SP1
LD
V2000
OUT
V40501
The LD instruction loads the data into the
accumulator. Since SP1 is used, this rung
automatically executes on every scan. You could
also use an X, C, etc. permissive contact.
The BIN instruction converts the accumulator data
to binary (you must omit this step if you have
already converted the data elsewhere).
ANDD
K0FFF
The ANDD instruction masks off the channel select
bits to prevent an accidental channel selection.
The OUT instruction sends the data to the module. Our
example starts with V40501, but the actual value
depends on the location of the module in your
application.
RST
Y34
OUT
Y37
Y37 is the output enable bit.
RST
Y36
Y34, Y35, Y36--OFF selects channel 1 for updating.
RST
Y35
Range
If the digital value is known
If the analog signal level is known.
4 – 20 mA
A = 16D + 4
4095
D = 4095 (A 4)
16
D = 4095 (A – 4)
16
D = 4095 (10mA – 4)
16
D = (255.93) (6)
D = 1536