DL205 Analog Manual, 7th Edition Rev. D
7-21
Chapter 7: F2-04THM, 4-Channel Thermocouple Input
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
B
C
D
Module Resolution 16-Bit (Unipolar Voltage Input)
Unipolar analog signals are converted into
65536 counts ranging from 0–65535 (2
16
).
For example, with a 0–156mV signal range,
78mV would be 32767. A value of 65535
represents the upper limit of the range.
H or L = high or low limit of the range
Module Resolution 15-Bit Plus
Sign(Bipolar Voltage Input)
The module has 16-bit unipolar or 15-bit
+ sign bipolar resolution. Bipolar analog
signals are converted into 32768 counts
ranging from 0–32767 (2
15
). For example,
with a -156mV–156mV signal range,
156mV would be 32767. The bipolar
ranges utilize a sign bit to provide 16-bit
resolution. A value of 32767 can represent
the upper limit of either side of the range.
Use the sign bit to determine negative
values.
H or L = high or low limit of the range
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
b
C
D
5
3
5
5
6
0
32767
0 V
78 mV
156mV
0V
2.5V
5V
Counts
Unipolar Resolution = H – L
65535
32767
32767
0
--5 V
0 V
5 V
--156 mV
0 V
156 mV
Counts
Bipolar Resolution = H – L
32767