DL205 Analog Manual, 7th Edition Rev. D
7-6
Chapter 7: F2-04THM, 4-Channel Thermocouple Input
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
B
C
D
Selecting the Number of Channels
The top two J7 jumpers labeled CH+1 and
CH+2 determine the number of channels that
will be used. The table shows how to set the
jumpers for channels 1 thru 4. The module
comes with both jumpers installed for four
channel operation. For example, to select
channels 1 thru 3, leave the CH+2 jumper
installed and remove the CH+1 jumper.
Any unused channels are not processed. For
example, if channels 1 thru 3 are selected,
channel 4 will not be active.
Setting Input Type
The next four jumpers: Tc Type 0, Tc Type 1, Tc Type 2, and Tc Type 3, must be set to match
either the type of thermocouple being used or the input voltage level. Since the module can be
used with many types of thermocouples, use the table to determine the proper settings for the
thermocouple being used.
The module comes from the factory with all four jumpers installed for use with a J type
thermocouple. To use a K type thermocouple, remove the jumper labeled Tc Type 0.
NOTE:
All channels of the module must be the same thermocouple type or voltage range.
X = Jumper installed, and blank space = jumper removed.
*NOTE:
R Wide is only available on modules with date code 0410E2 and later.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
b
C
D
Number of
Channels
Jumper
CH+1
CH+2
1
–
–
2
X
–
3
–
X
4
X
X
X = jumper installed
Blank space = jumper removed
Thermocouple/
Voltage Inputs
Jumper
Tc Type 0
Tc Type 1
Tc Type 2
Tc Type 3
J
X
X
X
X
K
–
X
X
X
E
X
–
X
X
R
–
–
X
X
R Wide*
–
X
–
–
S
X
X
–
X
T
–
X
–
X
B
X
–
–
X
N
–
–
–
X
C
X
X
X
–
0-5V
–
X
X
–
±5V
X
–
X
–
0–156 mV
–
–
X
–
±156 mV
X
X
–
–
Содержание DL205
Страница 1: ...DL205 Analog I O Manual Manual Number D2 ANLG M ...
Страница 2: ...Notes ...
Страница 6: ...Notes ...