Name
Range
Step
Default
Description
2nd
knee
point
voltage
(Ux2)
0.00…150.00%U
n
0.01%U
n
100%U
n
The higher voltage limit.
When this value is higher than Ux1, the function operates as voltage-
restrained overcurrent protection. If the two values are equal, the
function operates as voltage-controlled overcurrent protection.
The pick-up activation of the function is not directly equal to the START signal generation of the
function. The START signal is allowed if the blocking condition is not active.
Read-only parameters
The relay's
Info page displays useful, real-time information on the state of the protection function. It is
accessed either through the relay's HMI display, or through the setting tool software when it is
connected to the relay and its Live Edit mode is active.
Table. 5.3.20 - 171. Information displayed by the function.
Name
Range
Step
Description
Iv> condition
0: Normal
1: Start
2: Trip
3: Blocked
-
Displays status of the protection function.
Expected
operating
time
0.000...1800.000s
0.005s
Displays the expected operating time when a fault occurs. When IDMT
mode is used, the expected operating time depends on the measured
highest phase current value. If the measured current changes during a
fault, the expected operating time changes accordingly.
Time
remaining to
trip
-1800.000...1800.000s 0.005s
When the function has detected a fault and counts down time towards a
trip, this displays how much time is left before tripping occurs.
Voltage
measurement
0: Invalid U1 not avail.
1: Ok
-
If phase voltages are not available the function is not able to calculate
positive sequence voltage (U1). This can happen when voltage
measurement mode has been set to "3LL+U4" or "2LL+U3+U4" mode
but none of the channels have been set to "U0" mode.
I> pick-up
level now
0.00...1250.00xIn
0.01xIn
Overcurrent pick-up level used by the function at the moment. The pick-
up level changes with positive sequence voltage setting changes.
Measured
voltage now
0.00...1250.00%Un
0.01%Un Calculated positive sequence voltage at the moment. This influences
the overcurrent pick-up level used by the function.
I
meas
/I
set
at
the moment
0.00...1250.00
0.01
The ratio between the highest measured phase current and the pick-up
value.
Function blocking
The block signal is checked in the beginning of each program cycle. The blocking signal is received
from the blocking matrix in the function's dedicated input. If the blocking signal is not activated when
the pick-up element activates, a START signal is generated and the function proceeds to the time
characteristics calculation.
If the blocking signal is active when the pick-up element activates, a BLOCKED signal is generated and
the function does not process the situation further. If the START function has been activated before the
blocking signal, it resets and processes the release time characteristics similarly to when the pick-up
signal is reset.
The blocking of the function causes an HMI display event and a time-stamped blocking event with
information of the startup voltage values and its fault type to be issued.
A
AQ
Q-G215
-G215
Instruction manual
Version: 2.04
249
Содержание AQ-G215
Страница 1: ...AQ G215 Generator protection IED Instruction manual ...
Страница 399: ...Figure 7 4 241 Example block scheme A AQ Q G215 G215 Instruction manual Version 2 04 398 ...
Страница 421: ...Figure 8 14 264 Panel cutout dimensions and device spacing A AQ Q G215 G215 Instruction manual Version 2 04 420 ...
Страница 456: ...10 Ordering information A AQ Q G215 G215 Instruction manual Version 2 04 455 ...