The function outputs the START, TRIP and BLOCKED signals which can be used for direct I/O
controlling and user logic programming. The function generates general time-stamped ON/OFF events
to the common event buffer from each of the three (3) output signals. In the instant operating mode the
function outputs START and TRIP events simultaneously with an equivalent time stamp. The time stamp
resolution is 1 ms. The function also a resettable cumulative counter for the START, TRIP and
BLOCKED events.
The following figure presents a simplified function block diagram of the power protection function.
Figure. 5.3.15 - 138. Simplified function block diagram of the power protection function.
Measured input
The function block uses three-phase power values (active, reactive, or apparent). A -20 ms averaged
value is used for pre-fault data registering. The used power measurement value depends on user input.
If the protection relay has more than one CT module, the
Measured side parameter determines which
current measurement is used for power measurement.
Table. 5.3.15 - 134. Measurement inputs of the power protection function.
Signal
Description
Time base
3PH active power (P)
Total three-phase active power
5ms
3PH reactive power (Q)
Total three-phase reactive power
5ms
3PH apparent power
Total three-phase apparent power
5ms
Pick-up
The PQS>/< setting parameter controls the pick-up of the power protection function. This defines the
maximum or minimum allowed measured three-phase power (active, reactive, or apparent) before
action from the function. The function constantly calculates the ratio between the PQS>/< and the
measured power magnitude. The reset ratios of 97 % (pick-up mode "Over") and 103 % (pick-up mode
"Under") are built into the function and is always relative to the pick-up value.
A
AQ
Q-G215
-G215
Instruction manual
Version: 2.04
197
Содержание AQ-G215
Страница 1: ...AQ G215 Generator protection IED Instruction manual ...
Страница 399: ...Figure 7 4 241 Example block scheme A AQ Q G215 G215 Instruction manual Version 2 04 398 ...
Страница 421: ...Figure 8 14 264 Panel cutout dimensions and device spacing A AQ Q G215 G215 Instruction manual Version 2 04 420 ...
Страница 456: ...10 Ordering information A AQ Q G215 G215 Instruction manual Version 2 04 455 ...