If the blocking signal is active when the pick-up element activates, a BLOCKED signal is generated and
the function does not process the situation further. If the START function has been activated before the
blocking signal, it resets and processes the release time characteristics similarly to when the pick-up
signal is reset.
The blocking of the function causes an HMI display event and a time-stamped blocking event with
information of the startup power values and its fault type to be issued.
The blocking signal can also be tested in the commissioning phase by a software switch signal when
the relay's testing mode "Enable stage forcing" is activated (
General
→
Device).
The variables the user can set are binary signals from the system. The blocking signal needs to reach
the device minimum of 5 ms before the set operating delay has passed in order for the blocking to
activate in time.
Operating time characteristics for trip and reset
This function supports definite time delay (DT). For detailed information on this delay type please refer
to the chapter "General properties of a protection function" and its section "Operating time
characteristics for trip and reset".
Events and registers
The underexcitation function (abbreviated "UEX" in event block names) generates events and registers
from the status changes in START, TRIP and BLOCKED. The user can select which event messages
are stored in the main event buffer: ON, OFF, or both.
The events triggered by the function are recorded with a time stamp and with process data values.
Table. 5.3.18 - 160. Event codes.
Event number
Event channel
Event block name
Event code
Description
6976
109
UEX1
0
Start ON
6977
109
UEX1
1
Start OFF
6978
109
UEX1
2
Trip ON
6979
109
UEX1
3
Trip OFF
6980
109
UEX1
4
Block ON
6981
109
UEX1
5
Block OFF
The function registers its operation into the last twelve (12) time-stamped registers. The register of the
function records the ON event process data for START, TRIP or BLOCKED. The table below
presents the structure of the function's register content.
Table. 5.3.18 - 161. Register content.
Date and time
Event code
Trigger
power (P&Q)
Fault power
(P&Q)
Pre-fault
power (P&Q)
Trip time
remaining
Used SG
dd.mm.yyyy
hh:mm:ss.mss
6976-6981 Descr. Start average
power
Trip -20ms
averages
Start -200ms
averages
0 ms...1800s
Setting group
1...8 active
A
AQ
Q-G215
-G215
Instruction manual
Version: 2.04
241
Содержание AQ-G215
Страница 1: ...AQ G215 Generator protection IED Instruction manual ...
Страница 399: ...Figure 7 4 241 Example block scheme A AQ Q G215 G215 Instruction manual Version 2 04 398 ...
Страница 421: ...Figure 8 14 264 Panel cutout dimensions and device spacing A AQ Q G215 G215 Instruction manual Version 2 04 420 ...
Страница 456: ...10 Ordering information A AQ Q G215 G215 Instruction manual Version 2 04 455 ...