Pick-up
The
Q
set
< setting parameter controls the pick-up of the Q< function. This defines the minimum allowed
measured three-phase reactive power before action from the function. The function constantly
calculates the ratio between the
Q
set
< and the measured magnitude (Q
m
). The reset ratio of 97 % is
built into the function and is always relative to the
Q
set
< value.
Table. 5.3.18 - 158. Pick-up settings.
Name
Range
Step
Default
Description
Qset mode
0: Fixed
1: P-
dependent
-
0: Fixed
Decides whether the pick-up area is defines only by the
Q
set
< parameter
or by two points set in the PQ plane.
Qset<
0.0…-100
000kvar
0.01kvar -100kvar
In Fixed mode: sets the pick-up value for the function.
In P-dependent mode: chooses the reactive power for the first point.
Pick-up P1
for Qset<
0.0…-100
000kW
0.01kW
100kW
The value of the active power for
Q
set
< when the P-dependent mode is
in use.
Qset2<
0.0…-100
000kvar
0.01kvar -100kvar Chooses the reactive power for the second point when the P-dependent
mode is in use.
Pick-up P2
for Qset<
0.0…-100
000kW
0.01kW
100kW
The value of the active power for
Q
set2
< when the P-dependent mode is
in use.
The pick-up activation of the function is not directly equal to the START signal generation of the
function. The START signal is allowed if the blocking condition is not active.
Read-only parameters
The relay's
Info page displays useful, real-time information on the state of the protection function. It is
accessed either through the relay's HMI display, or through the setting tool software when it is
connected to the relay and its Live Edit mode is active.
Table. 5.3.18 - 159. Information displayed by the function.
Name
Range
Step
Description
Q<
condition
0: Normal
1: Start
2: Trip
3: Blocked
-
Displays the status of the protection function.
Expected
operating
time
0.000...1800.000s
0.005s
Displays the expected operating time when a fault occurs.
Time
remaining
to trip
-1800.000...1800.000s
0.005s
When the function has detected a fault and counts down time
towards a trip, this displays how much time is left before tripping
occurs.
Q
meas
/Q
set
at the
moment
-1250.00...1250.00Q
m
/Q
set
0.01Q
m
/Q
set
The ratio between the measured reactive power and the pick-up
value.
Function blocking
The block signal is checked in the beginning of each program cycle. The blocking signal is received
from the blocking matrix in the function's dedicated input. If the blocking signal is not activated when
the pick-up element activates, a START signal is generated and the function proceeds to the time
characteristics calculation.
A
AQ
Q-G215
-G215
Instruction manual
Version: 2.04
240
Содержание AQ-G215
Страница 1: ...AQ G215 Generator protection IED Instruction manual ...
Страница 399: ...Figure 7 4 241 Example block scheme A AQ Q G215 G215 Instruction manual Version 2 04 398 ...
Страница 421: ...Figure 8 14 264 Panel cutout dimensions and device spacing A AQ Q G215 G215 Instruction manual Version 2 04 420 ...
Страница 456: ...10 Ordering information A AQ Q G215 G215 Instruction manual Version 2 04 455 ...