Figure. 5.5.1 - 212. Simplified function block diagram of the CTS function.
Measured input
The function block uses analog current measurement values, the RMS magnitude of the current
measurement inputs, and the calculated positive and negative sequence currents. The user can select
what is used for the residual current measurement: nothing, the I01 RMS measurement, or the I02
RMS measurement.
Table. 5.5.1 - 230. Measured inputs of the CTS function.
Signal
Description
Time base
IL1RMS
RMS measurement of phase L1 (A) current
5ms
IL2RMS
RMS measurement of phase L2 (B) current
5ms
IL3RMS
RMS measurement of phase L3 (C) current
5ms
I01RMS
RMS measurement of residual input I01
5ms
A
AQ
Q-G215
-G215
Instruction manual
Version: 2.04
337