Technical Data
16
MAXXfl o EVO 150/302
EXAMPLE 3: MAXXFLO EVO & STORAGE TANK (SCHEMATIC)
Menu
Parameter
Settings
Confi guration
6020
Set function of extension module 1 to “Multifunctional”
6030
Set Relay Output QX21 module 1 to “dT controller 1 K21”
6041
Set sensor input BX22, module 1 to “Special temperature sensor 1”
General func-
tions
5570
Factory setting : Not used
5571
Factory setting: “- 1.5
O
C” - When BUFFER SS300-10 tank temperature is 0.5
O
C below
MAXXfl o EVO tank temperature K21 pump will be turned off .
5572
Factory setting: “3.0
O
C” - When BUFFER SS300-10 tank temperature is less than 2.0
O
C
below MAXXfl o EVO tank temperature K21 pump will be turned on.
5573
Factory setting : “DHW sensor B3”
5574
Factory setting : “Special temperature sensor 1”
5575
Factory setting : 30 seconds - Represents the minimum time that K21 pump will be activated
even if parameter 5571 conditions are met.
Related settings table (in addition to example 1 table)
3.5 SYSTEM SCHEMATIC EXAMPLES (CONTINUED)
(
+
0
%;
%;
8
0
0
RG
XOH
1
R
/
1 4;
4;
4;
1
1
(
/ 1 3( / 1
12
1&
&2
12
1&
&2
12
1&
&2
Q4 DHW
Circulation
pump
1 amp Max
(supplied by
others)
Buff er SS300-10
ST1 10k (B3977)
Tank sensor
K21 Transfer pump
1 amp Max
(Supplied by others)
AGU2.5 Expansion module
(supplied with Buff er SS300-10)
B39
DHW return
sensor kit
(optional)
p/no: 7720071