Technical Data
14
MAXXfl o EVO 150/302
Refer to “Controls Operating Instruction Manual for greater detail of the Anti-legionella function
setup
EXAMPLES 1 & 2: SINGLE AND PARALLEL MAXXfl o EVO (SETUP)
Menu
Parameter
Settings
DHW
1647
Legionella function
circulation pump
If the function is turned OFF, circulation pump Q4 will be switched OFF while the “Legionella”
function is performed (anti-legionella action performed on tank only).
If the function is turned ON, circulation pump Q4 is switched ON while the “Legionella” func-
tion is performed (anti-legionella action performed on DHW system).
1660
Pump release
Set desired option for activation of the DHW circulation pump, normally either activated with
time program 4 (DHW) or independently of DHW via time program 5
1661
Pump cycling
When switched on, the circulation pump Q4 will cycle on and off during the activation period
(on for 10 minutes then off for 20 minutes repeatedly).
Where B39 sensor has been installed this function will become active only once the circula-
tion setpoint has been achieved
1663
Circulation setpoint
When B39 sensor is installed on the DHW distribution return pipe, the heater controller will
monitor the return temperature during the activation time of the circulation pump Q4. When-
ever the temperature acquired by the sensor falls below the circulation setpoint, circulation
pump Q4 will be active until the setpoint has been exceeded (minimum pump run time is 10
minutes).
During a legionella cycle operation the temperature at the sensor can be used to adjust the
dwell time, ensuring that the entire DHW system reaches the legionella setpoint for the total
dwell time length set. The dwell time counter is not started until the temperature at the sensor
reaches legionella setpoint.
Main related parameter settings:
3.5 SYSTEM SCHEMATIC EXAMPLES (CONTINUED)
(
/ 1 3( / 1
12
1&
&2
12
1&
&2
12
1&
&2
Q4 DHW
circulation
pump
1 amp max
(supplied by others)
B39
DHW return
sensor kit
(optional)
p/no: 7720071