Maintenance
84
MAXXfl o EVO 150/302
Error
Code
Error Code Description
Diag.
Code
Notes
384
Extraneous light
252
393
Ionisation current detected before whilst in standby mode.
Check ionisation current (“Diagnostics producer” parameter
8329). If the current present is greater than 0.61 whilst the
burner is in standby, turn off the gas supply to check gas valve
is closing completely. If current is still present, remove ionisation
probe and use a screwdriver to clear the opening through the
burner door before replacing the probe and testing again.
Persistent errors may indicate that the burner is only operational
for very short periods. Try increasing the switching di
ff
erential by
at least 1
O
C (parameter 5024) to increase burner run time.
Other
Ionisation current detected during ignition phase before the gas
valve is opened.
385
Mains under voltage
554
555
Mains voltage below 185v - check electrical supply to the appli-
ance.
386
Fan speed tolerance
388
Fan outside allowed speed tolerance during standby phase
531
389
Fan outside allowed speed tolerance during pre-purge phase
374
383
384
Fan outside allowed speed tolerance during ignition phase.
375
386
Fan outside allowed speed tolerance during min modulation
phase.
385
Fan outside allowed speed tolerance during max modulation
phase.
532
534
382
390
Fan outside allowed speed tolerance during post-purge phase
Other
Check connections and wiring loom of the fan. Replace fan if no
fault found. If necessary use parameter 9650 Chimney drying
mode to test the function of the fan without having to operate the
burner
432
Function earth not connected
No Ignition earth, X1 / X17 not connected or earth fault. Check
internal and external earth wiring to the heater
433
Heat exchange temperature
Any
Heat exchanger temperature is too high. Investigate all sources
of overheating. When the issue has been resolved examine the
heat exchanger for damage before putting back into operation.
NA
DHW Operating mode locked
- Cannot operate in DHW
mode (No fault displayed)
Any
Remote system enable operating. Check to see if link wire is
still in place or controls wired to these terminals are closing this
circuit. When the appliance is operating via the volt free enable
signal, it is not possible to operate the appliance manually via
the GUI if the signal is not enabled (circuit closed).
6.6 ERROR CODES (CONTINUED)
Содержание 7800597
Страница 2: ...General 2 MAXXflo EVO 150 302 Blank Page ...
Страница 19: ...Technical Data 19 MAXXflo EVO 150 302 PCB2 3 6 WIRING DIAGRAM MAXXflo EVO 150 kW MODEL ...
Страница 86: ...Blank page ...
Страница 87: ...Blank page ...
Страница 88: ...April 2022 FM00866 EMS514880 13755 M10419 Rev A April 2022 ...