Maintenance
69
MAXXfl o EVO 150/302
6.2.13 CIRCULATION PUMP Q1
• Close the shut off valve before and after the pump (see 6.2.12)
• Use the drain points between the shut off valves to remove water from the pump.
• Remove the PWM and power connectors, using a small fl at blade screwdriver to lift the white tab before
pulling each connector free.
• Carefully undo the unions at the top and bottom of the pump body and remove pump.
• Fit the new pump seals
• Replacement is the reverse
• Refi ll and bleed air from the pipe work.
• Operate the pump for at least 1 minute by disconnecting the electrical connector from the heat exchanger
front fl ow sensor (B2)
• When all sound of air has stopped, reconnect B2 sensor and press the reset for around one second.
6.2.14 WATER PRESSURE SENSOR
• Close both water shut-off valves and use one of the drain points to drain down water until no further release
of water occurs.
• Carefully remove wiring connector from the sensor - using a small screwdriver to gently lift the tabs on each
side of the connector in turn, whilst at the same time gently pulling on the connector
• Pull out the metal locking clip, and keep to one side
• Turn and pull out sensor
• Replacement is the reverse
B2 Sensor
B
Connector locking
tabs
Pull connector
away from sensor
body
Metal locking clip
Pump Union
Pump Union