Commissioning
51
MAXXfl o EVO 150/302
5.5 FINAL CHECKS & USER HANDOVER
5.5.1 SETTING THE TIME CLOCK AND DHW TIME PROGRAM
NB. The DHW time clock is factory programmed to optimise this heaters e
ffi
ciency at the declared
load pro
fi
le under Eco-design Regulations.
It is essential that the time / date is set correctly and the DHW operation times have been pro-
grammed according to the requirements of the end user. Refer to the instruction sheet
“QUICK
START GUIDE”
or section 2.2 onwards of the
“CONTROLS OPERATING INSTRUCTIONS
MAN-
UAL”
for guidance on how to setup the controls
.
5.5.2 CHECKING THE DHW TANK SENSOR POSITION
For optimum control of DHW tank temperature, ensure that the tank sensor is touching the end of the sensor
well.
The sensor and sensor well can be located behind an access panel (A) at low level on the left hand side of the
heater. Remove 2x fi xings that secure the access panel to the side panel. Pull the sensor cable outwards a little
above the ‘P’ clip (B) position and feel if the cable springs back under cable tension and is pushed all the way
in. You should be able to feel the sensor bottom out against the end of the sensor well which is approx. 150mm
deep. Arrange the cable as below in the photo which maintains the cable under tension and also prevents the
sensor from being pulled out of the well.
A
B