Maintenance
65
MAXXfl o EVO 150/302
6.2.8 GAS VALVE
• Turn off the gas supply at the burner gas cock isolator
• Carefully remove the electrical connectors of the gas valve
• Remove the allen bolts securing the gas pipe to the valve
• Release the gas valve from the venturi by undoing three cap screws
• Transfer the rubber gasket to the new gas valve and orifi ce if fi tted .
• Replacement is the reverse.
• Operate the heat engine and check for gas leaks.
• After fi ve minutes check the rate and combustion is correct to the Data table. (
page 11
). Adjust using
the throttle adjustment screw on the gas valve if necessary. Turn clockwise to decrease CO
2
, anti-
clockwise to increase CO
2
(
see 5.0 for details)
NB Valve Coil resistances are 2.8k and 1.6k ohms
6.2.8 ELECTRODE REMOVAL
These are located on the front of the heat exchanger.
• Carefully pull off the electrical connectors.
• Undo the two screws retaining the bracket and withdraw.
• Replacement is the reverse ensuring that the gasket seal is placed correctly and is in good condition.
Ionisation electrode
Spark electrode
Io
I
Electrical connector
4 x securing bolts
4
4
Remove venturi cap screws
E