Installation
23
MAXXfl o EVO 150/302
4.4 UNVENTED DESIGN
DANGER
Unvented systems should only be fi tted by an approved installer
When using the heater on an unvented hot water storage system, the Unvented System Kit, part number
7726954, available from the manufacturer
must
be fi tted. When used in an unvented system, the heater will
supply hot water at a maximum of 6 bar or at the pressure available at the mains feed if this is lower. During con-
ditions of no-fl ow, system pressure may rise to a maximum of 8 bar, whilst the burner is operating. When testing
the system, it is recommended that a maximum test pressure
of 9 bar
is used.
For the hot water supply
, a 24 litre expansion vessel is suitable for the stored volume of all models and an
average pipework system. For systems with larger pipe volumes or additional storage, expansion vessels with
greater capacity are available. Assemble the components of the unvented system kit as shown below
When assembling the Pressure Reducing Valve and Double Non-Return Valve, ensure that the
fl
ow arrows marked on the
components are pointing in the direction of
fl
ow, that is towards
the heater.
The relief valves fi tted to this heater must not be used for any other purpose. No fi tting should be installed be-
tween the expansion valve and the cylinder. The cold water for services may be drawn from the 22mm com-
pression port up stream of the Pressure Reducing Valve. The water pressure at this point will be similar to that
available at the hot water outlet of the water heater. If higher fl ow rates are required for the cold water services, a
suitable tee fi tting should be fi tted to the pipework, upstream of the Pressure Reducing Valve.
All fi ttings and materials supplying water to the storage vessel must be suitable for use with drinking water and
listed in the current Water Research Centre “Materials and Fittings Directory”. Installation of unvented hot storage
water systems must comply with Part G of Schedule 1 of the Building Regulations.
Expansion vessel
Expansion vessel
(24 litre)
(24 litre)
Through fl ow valve
Through fl ow valve
One piece inlet control
One piece inlet control
(6 bar pressure reducing
(6 bar pressure reducing
valve, check valve & 8 bar
valve, check valve & 8 bar
pressure relief valve)
pressure relief valve)
Temperature & pressure relief valve
Temperature & pressure relief valve
(Factory fi tted)
(Factory fi tted)
10 bar
10 bar 95˚˚C
Tundish
Tundish
(supplied with heater)
(supplied with heater)
Cold
Cold
water
water
feed
feed
To drain
To drain
DHW
DHW
7726954 Unvented kit
Secondary Return
Secondary Return
Содержание 7800597
Страница 2: ...General 2 MAXXflo EVO 150 302 Blank Page ...
Страница 19: ...Technical Data 19 MAXXflo EVO 150 302 PCB2 3 6 WIRING DIAGRAM MAXXflo EVO 150 kW MODEL ...
Страница 86: ...Blank page ...
Страница 87: ...Blank page ...
Страница 88: ...April 2022 FM00866 EMS514880 13755 M10419 Rev A April 2022 ...