Installation
34
MAXXfl o EVO 150/302
4.7.13
FLUE TERMINAL POSITIONS - C
13
C
33
C
53
C
63
TYPE (CONCENTRIC / TWIN)
Code Description
Min distance (mm)
A
Directly below an opening, air brick, opening window etc
2,500
B
Above an opening, air brick, opening window etc
1,100
C
Horizontally to an opening, air brick, opening window etc
1,100
D
Below gutters, soil pipes or drainpipes
200
E
Below eaves
200
F
Below a balcony or car port roof
*not recommended
G
Above ground, roof or balcony level
300**
H
From vertical drain or soil pipe
150
J
From an internal or external corner to a fl ue terminal alongside a
boundary
300**
K
From a terminal facing a terminal
3,350
L
Vertically from a terminal on the same wall
2,500
M
Horizontally from a terminal on the same wall
1,100
N
From a surface or a boundary line facing a terminal
3,860
P
From a opening in a carport (e.g. door, windows) into the building
*not recommended
Q
Above apex of a pitched roof
620
R
From an adjacent wall (edge of terminal) or a vertical structure on a
roof
620**
S
Above a fl at roof
620
From any other roof fl ue terminal
1,100
* Risk assessment required
** Plume management recommended
Figures for guidance only, for full details refer to IGEM/UP/10 edition 4
Terminals should be so
positioned as to avoid
products of combustion
entering openings into
buildings or other
fl
ues or
vents