11. Timing Chart (1-axis Type)
11-3
When 0=Setup parameter of the function menu is set as follows:
1
Disp Measure Mode setting: SYNC(0)
2
LS Input Validity setting: Invalid(1)
3
Self Hold Validity setting: Valid(0)
13ms
2ms
2ms
2ms
1ms
1ms
3ms
2ms
3ms
5ms
1ms
1ms
1ms
1ms
1ms
3ms
Before Weld Force measurement position
Before Weld Work measurement position
(*3)
(*3)
(*6)
(*1)
(*2)
(*4)
ST-DISP1 input
GOOD output(*5)
FINISH output(*5)
NG output(*5)
(Weld Start output)
Hold-Time(setting)
Weld-Time(setting)
Squeeze-Time(setting)
Displacement measurement
After Weld Force measurement
After Weld Work measurement
Before Weld Force measurement
Before Weld Work measurement
20ms min.
LEV-FORCE1 set force
LEV-DISP1 set displacement
Displacement change
Force change
Vibration check
Welding(power supply)
SV11 to 13 output
LEV-FORCE11 to 13 output(*7)
LEV-DISP11 to 13 output(*7)
After Weld Work
measurement position
After Weld Force
measurement position
*1 When Self Hold Validity is set to Invalid(1), hold the ST-DISP input until the
vibration check ends.
*2 Varies depending on the allowable vibration range setting and vibration stability
time.
*3 The output time of Before/After Weld Time varies depending on settings of Force
Sampling and Force Average.
*4 Set the time longer than the total weld time of welding machine for Weld-Time.