I/O Configuration
Input filtering is configured using RSLogix 500/RSLogix Micro
programming software. To configure the filters using RSLogix 500/
RSLogix Micro:
1.
Open the Controller folder.
2.
Open the I/O Configuration folder.
3.
Open slot 0 (controller).
4.
Select the Embedded I/O Configuration tab.
The input groups are pre-arranged. Select the filter time required for each
input group. Apply a unique input filter setting to each of the input
groups:
The minimum and maximum response times associated with each input
filter setting can be found in your controller’s
Analog Inputs
The MicroLogix 1400 -L32BWAA, -L32AWAA, and -L32BXBA support
4-channel, 12-bit resolution analog input with four 12-bit resolution
analog input channels. These channels are single-ended (unipolar) circuits
and accept 0…10V DC.
Input words 4…7 contain the value of analog inputs (Word 4: analog
input channel 0, Word 5: analog input channel 1, Word 6: analog input
channel 2, Word 7: analog input channel 3).
MicroLogix 1400 Input Groups
Controller
MicroLogix 1400
Input Groups
•
0 and 1
•
2 and 3
•
4 and 5
•
6 and 7
•
8 and 9
•
10 and 11
•
12 and 13
•
14 and 15
•
16…23
•
24 to xxxx (reserved)