Publication 1766-RM001A-EN-P - October 2008
I/O Configuration 27
I/O Addressing
Addressing Details
The I/O addressing scheme and examples are shown below.
(1) I/O located on the controller (embedded I/O) is slot 0.
I/O added to the controller (expansion I/O) begins with slot 1.
Xd:s.w/b
File Type
Input (I) or Output (O)
Data File Number Slot Number
(1)
Word
Bit
Bit Delimiter
Word Delimiter
Slot Delimiter
I/O addressing scheme
Format
Explanation
Od:s.w/b
Id:s.w/b
X
File Type
Input (I) or Output (O)
d
Data File Number
(optional)
0 = output, 1 = input
:
Slot delimiter
(optional, not required for Data Files 2…255)
s
Slot number (decimal)
Embedded I/O: slot 0
Expansion I/O:
slots 1…7 for MicroLogix 1400 (See page 17 for an illustration.)
.
Word delimiter. Required only if a word number is necessary as noted below.
w
Word number
Required to read/write words, or if the discrete bit number is above 15.
Range: 0…255
/
Bit delimiter
b
Bit number
0 to 15
Addressing examples
Addressing Level
Example Address
(1)
Slot
Word
Bit
Bit addressing
O:0/4
(2)
Output slot 0 (embedded I/O)
Word 0
Output bit 4
O:2/7
Output slot 2 (expansion I/O)
Word 0
Output bit 7
I:1/4
Input slot 1 (expansion I/O)
Word 0
Input bit 4
I:0/15
Input slot 0 (embedded I/O)
Word 0
Input bit 15