I/O Configuration
Embedded I/O
The MicroLogix 1400 provide discrete I/O and analog input that is built
into the controller as listed in the following table. These I/O points are
referred to as Embedded I/O.
AC embedded inputs have fixed input filters. DC embedded inputs have
configurable input filters for a number of special functions that can be
used in your application. These are: high-speed counting, event input
interrupts, and latching inputs. The 1766-L32BXB and 1766-L32BXBA have
three high-speed outputs for use as pulse train output (PTO) and/or pulse
width modulation (PWM) outputs.
Catalog
Number
Description
Input
Power
User
Power
Embedded
Discrete I/O
Embedded
Analog I/O
Comm.
Ports
1766-L32BWA
100/240V AC
24V DC
12 Fast 24V DC Inputs
8 Normal 24V DC Inputs
12 Relay Outputs
None
1 RS232/RS485
(1)
1 Ethernet
1 RS232
(2)
1766-L32AWA
None
20 120V AC Inputs
12 Relay Outputs
1766-L32BXB
24V DC
12 Fast 24V DC Inputs
8 Normal 24V DC Inputs
6 Relay Outputs
3 Fast DC Outputs
3 Normal DC Outputs
1766-L32BWAA
100/240V AC
24V DC
12 Fast 24V DC Inputs
8 Normal 24V DC Inputs
12 Relay Outputs
4 Voltage Inputs
2 Voltage Outputs
1766-L32AWAA
None
20 120V AC Inputs
12 Relay Outputs
1766-L32BXBA
24V DC
12 Fast 24V DC Inputs
8 Normal 24V DC Inputs
6 Relay Outputs
3 Fast DC Outputs
3 Normal DC Outputs
(1)
Isolated RS-232/RS-485 combo port. Same as ML1100 Comm 0
(2)
Non-isolated RS-232. Standard D-sub connector