Publication 1766-RM001A-EN-P - October 2008
580
Fault Messages and Error Codes
0015
I/O CONFIGURATION
FILE ERROR
The user program I/O configuration
is invalid.
Non-User
Re-compile and reload the program, and enter
the Run mode. If the error persists, be sure to
use RSI programming software to develop
and load the program.
0016
STARTUP
PROTECTION FAULT
The user fault routine was executed
at power-up, prior to the main ladder
program. Bit S:1/13 (Major Error
Halted) was not cleared at the end of
the User Fault Routine. The User
Fault Routine ran because bit S:1/9
was set at power-up.
Recoverable
•
Either reset bit S:1/9 if this is consistent
with the application requirements, and
change the mode back to RUN, or
•
clear S:1/13, the Major Error Halted bit,
before the end of the User Fault Routine.
0017
NVRAM/MEMORY
MODULE USER
PROGRAM
MISMATCH
Bit S:2/9 is set in the controller and
the memory module user program
does not match the controller user
program.
Non-Recoverable
Transfer the memory module program to the
controller and then change to Run mode.
0018
MEMORY MODULE
USER PROGRAM
INCOMPATIBLE WITH
OS
The user program in the memory
module is incompatible with the OS.
Non-User
•
Upgrade the OS using ControlFlash to be
compatible with the memory module.
•
Obtain a new memory module.
•
Contact your local Rockwell Automation
representative for more information about
available operating systems your controller.
001A
USER PROGRAM
INCOMPATIBLE WITH
OS AT POWER-UP
The user program is incompatible
with the OS.
Non-User
•
Upgrade the OS using ControlFlash.
•
Contact your local Rockwell Automation
representative for more information about
available operating systems your controller.
0020
MINOR ERROR AT
END-OF-SCAN
DETECTED
A minor fault bit (bits 0-7) in S:5 was
set at the end of scan.
Recoverable
•
Correct the instruction logic causing the
error.
•
Enter the status file display in your
programming software and clear the fault.
•
Enter the Run mode.
0021
Reserved
N/A
N/A
•
0022
WATCHDOG TIMER
EXPIRED, SEE S:3
The program scan time exceeded the
watchdog timeout value (S:3H).
Non-Recoverable
•
Determine if the program is caught in a loop
and correct the problem.
•
Increase the watchdog timeout value in the
status file.
0023
STI ERROR
An error occurred in the STI
configuration.
Recoverable
See the Error Code in the STI Function File for
the specific error.
0028
INVALID OR
NONEXISTENT USER
FAULT ROUTINE
VALUE
•
A fault routine number was
entered in the status file, number
(S:29), but either the fault routine
was not physically created, or
•
the fault routine number was less
than 3 or greater than 255.
Non-User
•
Either clear the fault routine file number
(S:29) in the status file, or
•
create a fault routine for the file number
reference in the status file (S:29). The file
number must be greater than 2 and less
than 256.
Error Codes
Error
Code
(Hex)
Advisory Message
Description
Fault
Classification
Recommended Action