Publication 1766-RM001A-EN-P - October 2008
Using the High-Speed Counter and Programmable Limit Switch
137
PLS Data File Definitions:
Once the values above have been entered for HIP and OHD, the
PLS is configured.
Configuring the HSC for Use with the PLS
1.
Under Controller, double-click on
Function Files
.
2.
For
HSC:0
, configure the HSC.MOD to use PLS10 and for the HSC to
operate in mode 00.
PLS Operation for This Example
When the ladder logic first runs, HSC.ACC equals 0, therefore
PLS10:0.OLD's data is sent through the HSC.OMB mask and sets all the
outputs off.
When HSC.ACC equals 250, the PLS10:0.OHD is sent through the
HSC.OMB mask and energizes the outputs.
This will repeat as the HSC.ACC reaches 500, 750, and 1000. Once
completed, the cycle resets and repeats.
Data
Description
Data Format
HIP
High Preset
32-bit signed integer
LOP
Low Preset
OHD
Output High Data
16-bit binary
(bit 15--> 0000 0000 0000 0000 <--bit 0)
OLD
Output Low Data
IMPORTANT
The value for MOD must be entered in Hexadecimal.
For example, PLS10 = 0A and HSC Mode = 00