Publication 1766-RM001A-EN-P - October 2008
Controller Memory and File Types
51
If the Memory Module User Program has the “Load Always” functionality
enabled, and the controller User Program has a password specified, the
controller compares the passwords before transferring the User Program
from the Memory Module to the controller. If the passwords do not match,
the User Program is not transferred and the program mismatch bit is set
(S:5/9).
Clearing the Controller
Memory
If you are locked out because you do not have the password for the
controller, you can clear the controller memory and download a new User
Program.
You can clear the memory when the programming software prompts you
for a System or Master Password to go on-line with the controller. To do
so:
1.
Enter 65257636 (the telephone keypad equivalent of MLCLRMEM,
MicroLogix Clear Memory).
2.
When the Programming Software detects this number has been
entered, it asks if you want to clear the memory in the controller.
3.
If you reply “yes” to this prompt, the programming software
instructs the controller to clear Program memory.
TIP
If a password is lost or forgotten, there is no way to bypass the password
to recover the program. The only option is to clear the controller’s memory.